5
Speed Search (C504)
6
PID Enable (C601)
7
DC Bus Control
8
PID Polarity (C602)
9
Temperature Control
selection (C310)
10-11
Reserved
12
Reverse Direction Lock
(B308)
13
Maintained/Momentary
Start (A302)
14
Display Loss Detect
Enable (C405)
15
Timer output Enable
(C308)
40497. Command Word
Access – Write Only
10
Resolution – 1
This parameter is used to start and stop the AC Drive.
Value
11
100
200
Amtech
11.20
current, when this protection is enabled.
= 0: Disable = 1: Enable
Enable or disable the speed Search operation.
= 0: Disable = 1: Enable
Enable or disable the PID control action.
= 0: Disable = 1: Enable
When enabled, it will control the deceleration time to prevent
the over voltage during deceleration condition.
= 0: Disable = 1: Enable
This can be used to invert the PID output.
= 0: Negative = 1: Positive
This parameter controls the automatic change of the carrier
frequency in case of temperature rise above the predefined
level.
= 0: Disable = 1: Enable
Set this to prevent unintentional reverse direction operation.
When enabled, ensure that forward direction is selected in
A305 (or at terminal). The AC DRIVE will not start otherwise.
= 0: Disable = 1: Enable
When using terminal start/ stop facility, this parameter gives
the choice of having maintained or momentary contacts for
start or stop.
= 0: The start control maintained type
= 1: The start/ stop control momentary type.
Enable or disable the operation panel communication loss
fault. If enabled, AC DRIVE will generate fault if it does not
receive any response from the operation panel within
100msec.
= 0: Disable = 1: Enable
Set the ON/OFF control for the timer output.
= 0: ON only when AC DRIVE is ON
= 1: ON whenever power is ON
Action
Start Drive
Stop Drive or Rest fault when fault is present