6.8. Requirements for transformers

6.8.1. Grid connection transformer

CAUTION
These units must be connected to a transformer with the neutral of the low-voltage side isolated, thus
generating an IT grid.
This section lists the technical specifications of the grid connection transformer which converts the medium or
high supply voltage to the operating voltage of the unit.
1.
The transformer's power must be greater than the sum of the power ratings of the connected inverters,
keeping in mind the locations environmental conditions and height.
If connecting the equipment to the transformer's same low voltage winding, these must be synchronized. These
2.
equipment have all the necessary elements to synchronize up to four inverters.
INFO
See section "13. Connection of the DCAC connections module" to proceed with connection.
48
Fuse holder base
size
3L
Fuse size
3L
3
Preparation for installing the unit
Fuse size
Rated current
250 A
315 A
350 A
NH3L
400 A
450 A
500 A
Rated current
200 A
250 A
315 A
350 A
400 A
Low Voltage / Medium
Voltage
ABQ2026IQE01_A - Installation and Operation Manual
Rated voltage
1500 VDC
Rated voltage
1500 VDC