Huawei FusionModule800 Installation Manual page 245

Smart small data center six fans
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
WebUI operating environment requirements:
Procedure
Step 1 Connect a network cable between the PC network port and the WAN_1 port (protected by a
security mechanism) on the ECC800.
Table 6-4
Table 6-4 Default IP addresses for the WAN and LAN ports on the ECC800
Port
WAN_1
WAN_2
LAN_1 and LAN_2
Step 2 Configure the PC IP address and the WAN_1 IP address in the same network segment.
If the port IP address is 192.168.1.10, subnet mask is 255.255.255.0, and default gateway is
192.168.1.1, set the PC IP address to 192.168.1.11, subnet mask to 255.255.255.0, and default
gateway to 192.168.1.1.
Step 3 Set LAN parameters.
1.
2.
3.
4.
5.
Issue 10 (2019-12-20)
The default user with operation rights is operator. The preset password is Changeme. The
operator user has no rights for parameter setting, control, and maintenance that may
affect system running.
Operating system: Windows 7 and later versions
Browser: Internet Explorer 8.0 and later versions; Firefox 38.0.5 and later versions;
Chrome 46.0.2490.80 and later versions
lists the default IP addresses for the WAN and LAN ports on the ECC800.
The WAN_1 port IP address cannot be set to an IP address in any of the following network
segments: 192.168.0.x, 192.168.8.x, 192.168.248.x, and 192.168.245.x.
IP addresses for the WAN_1 and WAN_2 ports should not be set in the same network
segment.
If the ECC800 connects to a LAN and a proxy server has been selected, perform
3.4.
If the ECC800 connects to the Internet, and the PC in a LAN accesses the Internet over a proxy
server, do not perform
Open the Internet Explorer and choose Tools > Internet Options.
Click the Advanced tab and select Use TLS1.1 and Use TLS1.2.
(Optional) Click the Connections tab and select LAN settings.
(Optional) Under Proxy server, clear Use a proxy server for your LAN.
Click OK.
Copyright © Huawei Technologies Co., Ltd.
Default IP Address
192.168.1.10
192.168.248.10
192.168.248.10 or 192.168.245.10 (with
Vlan tag 15)
Step 3.3
or
Step
3.4. Otherwise, you will fail to access the ECC800.
6 Power-On Commissioning
Step 3.3
and
Step
236

Advertisement

Table of Contents
loading

Table of Contents