Huawei FusionModule800 Installation Manual page 110

Smart small data center six fans
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
Applicable
No.
Scenario
8
9
10
11
12
Single smart
1
cooling
product or
double smart
cooling
products
Issue 10 (2019-12-20)
Cable
From
Name
power cable
J3 cable
X101,
X102, and
X103 ports
on the
indoor unit
X101,
J4 cable
X102, and
X103 ports
on the
indoor unit
T/H sensor
T/H sensor
cable
Energy
FE-2 port
control
on the
center 800
control unit
(ECC800)
cable
Ground
Ground
cable
point on the
smart
cooling
product
control unit
Electric
Converged
heater
cabinet
contactor
XT4-6 and
(required if
XT4-5
an electric
correspond
heater is
to smart
configured)
cooling
products 1
and 2,
respectively
Copyright © Huawei Technologies Co., Ltd.
To
Cable
Specifications
J3 port on the
N/A
smart cooling
product control
unit
J4 port on the
N/A
smart cooling
product control
unit
RS485/12 V
Two shielded
port on the
twisted pairs, 26
smart cooling
AWG
product control
unit
PoE port on the
Four shielded
smart ETH
twisted pairs, 24
gateway
AWG
IT cabinet
4 mm
ground cable
Contactor KM1
N/A
of the
corresponding
smart cooling
product
3 Hardware Installation
Remarks
Connected onsite
Connected onsite
Connected onsite
If the smart
ETH gateway
is configured,
connect the
cable to the
PoE port on
the smart ETH
gateway.
If no smart
ETH gateway
is configured,
connect the
cable to the
WAN_2 port
on the
ECC800.
2
Connected onsite
Factory-installed
101

Advertisement

Table of Contents
loading

Table of Contents