Installing The Vcn540 - Huawei FusionModule800 Installation Manual

Smart small data center six fans
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
Figure 3-118 Installing a VCN500
Step 4 Connect the VCN500 power cable to the appropriate PDU2000.
----End

3.11.4 Installing the VCN540

Context
Procedure
Step 1 Install a hard drive.
1.
2.
3.
4.
Issue 10 (2019-12-20)
The VCN540 does not carry disks when being delivered. First install disks and then
install the device in a network cabinet.
After the VCN540 is delivered to the site, disk filler panels are installed in slots where
disks are not installed, by default. You are not advised to remove the filler panels from
the slots where disks are not installed, because removing the filler panels will affect the
heat dissipation of fans and generate some noises.
Install a hard drive.
Secure the hard drive to the front panel using a screwdriver.
Push the hard drive into the subrack along the guide rails until it cannot move forwards.
Close the ejector lever and push the hard drive in position.
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation
128