Step 4 Take out the outdoor unit stop valve pipe from the outdoor unit fitting bag and connect the
pipe by referring to
Figure 3-63 Pipe ports on the outdoor unit
Step 5 Weld the routed pipe and the pipe port reserved outside the cabinet.
----End

3.7.7 Connecting Water Pipes

The water pipes to be connected onsite include humidifier water inlet pipes and condensate
drainpipes. Route pipes from the top or bottom based on site requirements.
Figure 3-64
Issue 10 (2019-12-20)
Step
3.1,
Connect the liquid pipe stop valve first, and then the gas pipe stop valve.
The outdoor unit has been charged 6 kg of R410A refrigerant before delivery, after the
outdoor unit stop valve pipe is installed, the stop valve plug should be closed. Open the
stop valve plugs of the outdoor unit gas pipe and liquid pipe after vacuumization is
complete to avoid refrigerant leaks.
shows the holes in the bottom of the smart cooling product.
Copyright © Huawei Technologies Co., Ltd.
Step
3.2, and
Step
3.3.
3 Hardware Installation
Figure 3-63
shows the valve installation.