3.11.10 Installing an AI/DI Module

If an AI/DI module is required, perform the following steps to install it.
Context
You are advised to deploy an AI/DI module at the 42 U position on the rear top of the IT
cabinet adjacent to the Converged Cabinet.
Figure 3-189 Installation position of an AI/DI module
Procedure
Step 1 Determine the mounting holes for the AI/DI module based on the IT cabinet layout. Engage
floating nuts into appropriate mounting holes in the rack rail of the cabinet using a floating
nut mounting bar. Install two floating nuts on each side.
Figure 3-190 Installing a floating nut
Step 2 Install the AI/DI module at the appropriate position in the IT cabinet.
Issue 10 (2019-12-20)
Press the lower part of the smart ETH gateway to clamp the smart ETH gateway onto the
guide rail.
Shake the smart ETH gateway in different directions to ensure that it is reliably installed.
Figure
If no floating nut mounting bar is available, using a flat-head screwdriver instead.
Ensure that the floating nuts on both sides are on the same horizontal line.