Figure A-8 Installing the tray
Step 3 Place the dehumidifier on the tray and move it to its installation place, and secure the
dehumidifier mounting ears to the rack rail using a floating nut mounting bar and three
floating nuts for each mounting ear, as shown in
Figure A-9 Installing floating nuts
Step 4 Secure the dehumidifier to the dehumidifier mounting ears on the rack rail using six M6
screws, as shown in
Issue 10 (2019-12-20)
If no floating nut mounting bar is available, using a flat-head screwdriver instead.
Ensure that the floating nuts on both sides are on the same horizontal line.
Floating nuts must be installed in mounting holes alternatively on the dehumidifier.