FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
Figure 2-1 Space requirements for a cold-aisle containment
Table 2-6 Cabinet information
Cabinet Type
IT cabinet
Converged Cabinet
Battery cabinet (deployed
inside the aisle
containment)
Battery cabinet (deployed
outside the aisle
containment)
Network cabinet
2.4 Installation Scenarios
Issue 10 (2019-12-20)
The Smart Module can be installed with one side against a wall.
Cabinets and aisle containments are assembled for delivery. The cabinet depth is 1350 mm.
The component layout illustrates only the positions of components. The actual component installation
positions prevail.
Copyright © Huawei Technologies Co., Ltd.
Dimensions (H x W x D)
2000 mm x 600 mm x 1350 mm
2000 mm x 600 mm x 1350 mm
2000 mm x 600 mm x 1350 mm
2000 mm x 600 mm x 1100 mm (or
1200 mm)
2000 mm x 600 mm x 1350 mm
2 Installation Preparations
Reference Net
Weight
160 kg
410 kg
160 kg
140 kg
160 kg
21