Figure 3-130 Address and DIP switch setting on a T/H sensor
Description about the cable connection to and DIP switch setting on a T/H sensor:
Issue 10 (2019-12-20)
Connect the T/H sensors in the shape of
in series.
Connect the T/H sensors in the shape of
in series.
Connect the T/H sensors in the shape of
in series.
Each of the T/H sensors connected in series has a unique address.
The DIP switch address for T/H A is always 21. T/H A connects to smart cooling product
control units 1 as the last T/H sensor connected in series.
The DIP switch address for T/H B is always 21. T/H B connects to smart cooling product
control units 2 as the last T/H sensor connected in series.
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation
to smart cooling product control unit 1
to smart cooling product control unit 2
to smart cooling product control unit 3