FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
Figure 3-27 Oil trap (unit: mm)
Gas Pipe, Liquid Pipe, and Thermal Insulation Foam (Optional)
Table 3-2
Table 3-2 Specifications
Item
Gas pipe
Liquid pipe
Thermal insulation foam
Water pipe
Figure 3-28
Issue 10 (2019-12-20)
lists the specifications for pipes and thermal insulation foam.
shows how to connect a drainpipe.
Copyright © Huawei Technologies Co., Ltd.
Specifications
5/8 inch (15.88 mm), wall thickness: 1.0 mm;
pressure withstanding capacity ≥ 4.5 MPa
3/8 inch (9.52 mm), wall thickness: 0.75 mm;
pressure withstanding capacity ≥ 4.5 MPa
≥ 13 mm