Step 1 Take the water inlet pipe out of the smart cooling product fitting bag. Route the pipe through
the water inlet hole at the bottom and connect the pipe to the water inlet solenoid valve, as
shown in
Check that the water inlet solenoid valve is tightened with 2-3 circles of screw threads
exposed.
Figure 3-66 Installing the humidifier water inlet pipe
Issue 10 (2019-12-20)
The object shown in the broken line box is the water inlet pipe connector with inner screw threads
delivered with smart cooling products. This object and the hose clamp (part 5) are configured in standard
configuration. Other parts are not configured and need to be purchased onsite.
Figure
3-66.
Copyright © Huawei Technologies Co., Ltd.
G 1/2 inch, connected to a rigid
pipe with outer screw threads
(5) Hose clamp
3 Hardware Installation
made of PP-R or
other material
(6) Hose: made of
EPDM or other
material
87