Huawei FusionModule800 Installation Manual page 79

Smart small data center six fans
Hide thumbs Also See for FusionModule800:
Table of Contents

Advertisement

FusionModule800 Smart Small Data Center
Installation Guide (Six Fans)
Multiple Outdoor Units
When multiple outdoor units are to be installed, if they cannot be installed against a wall or
the local outdoor temperature may be below –10° C (NetCol500-A018) or 0° C
(NetCol500-A020), place an air baffle at the air intake side of each outdoor unit.
Figure 3-48 Space requirements for installing multiple outdoor unit
Issue 10 (2019-12-20)
Figure 3-47 Requirements for installing an outdoor unit on a wall
The bearing capacity of the support platform is more than 230 kg.
Reserve no less than 300 mm from the left or right side of the outdoor unit for maintenance
personnel to walk.
Grid structure is recommended to avoid the air exhaust and intake of the smart cooling product being
affected by the guardrail structure.
The picture is only for reference, adjust based on the on-site situation if necessary.
Copyright © Huawei Technologies Co., Ltd.
3 Hardware Installation
70

Advertisement

Table of Contents
loading

Table of Contents