3. Installation
Selector plate positions
1
2
3
4
1) Reversible 2x3/2−way valves from Festo (identifier T32F−A, T32N−A, T32W−A) require operating
pressure at port (12) for the pneumatic spring function.
2) Note:
Positions 3 and 4 of the selector plate enable the ducted exhaust of the pilot exhaust air and
venting air if the valve terminal is not equipped with reversible 2x3/2−way valves from Festo.
The seals between the manifold sub−bases and the valves must be mounted in the appropriate
position (see Chapter 5.4.1). Note that the ducted exhaust of the pilot exhaust air and venting via
port (12) does not comply with standard ISO 15407−2 or 5599−2.
Tab. 3/2: Selector plate positions of the selector end plate type VABE−...RZ−...B1
Festo P.BE−VTSA−44−EN en 0905e
1)
Description
Selector plate position for pilot control with external pilot air
supply:
Pilot air is supplied via port (14)
Port (12) must be closed since ports (12) and (14) are con
nected internally.
The pilot air is exhausted unducted at the valves via the
valve housing.
Selector plate position for pilot control with internal pilot air
supply:
Pilot air supply branched from duct (1)
Ports (12) and (14) sealed
The pilot air is exhausted unducted at the valves via the
valve housing.
Selector plate position for pilot control with external pilot air
supply, ducted pilot exhaust and venting air:
Pilot air is supplied via port (14)
Pilot exhaust air (82/84) and venting air via port (12)
Selector plate position for pilot control with internal pilot air
supply, ducted pilot exhaust and venting air:
Pilot air supply branched from duct (1)
Pilot exhaust air (82/84) and venting air via port (12)
2)
2)
3−17