Main Menu - Communications And Options - Group - Danfoss VLT CDS 803 Programming Manual

Compressor drive
Hide thumbs Also See for VLT CDS 803:
Table of Contents

Advertisement

Parameters
6-92 Terminal 42 Digital Output
Select the function of Terminal 42 as an analog current output.
See also parameter 6-90 Terminal 42 Mode. See
parameter 5-40 Function Relay for description of the choices.
Option:
3
3
[25]
Reverse
[26]
Bus OK
[35]
External
Interlock
[36]
Control word
bit 11
[37]
Control word
bit 12
[41]
Below
reference, low
[42]
Above ref,
high
[44]
Oil boost
active
[45]
Bus Control
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital
output A
[81]
SL digital
output B
[82]
SL digital
output C
[83]
SL digital
output D
[160]
No alarm
[161]
Running
reverse
[165]
Local ref.
active
[166]
Remote ref.
active
[167]
Start
command
activ
[168]
Drive in hand
mode
[169]
Drive in auto
mode
40
®
VLT
Compressor Drive CDS 803
Function:
Danfoss A/S © 06/2019 All rights reserved.
6-93 Terminal 42 Output Min Scale
Range:
Function:
0 %
[0 - 200 %]
Scale for the minimum output (0
*
mA or 4 mA) of the analog signal
at terminal 42. Set the value to be
the percentage of the full range of
the variable selected in
parameter 6-91 Terminal 42 Analog
Output.
6-94 Terminal 42 Output Max Scale
Range:
Function:
100 %
[0 - 200 %]
Scale for the maximum output (20
*
mA) of the scaling at terminal 42.
Set the value to be the percentage
of the full range of the variable
selected in parameter 6-91 Terminal
42 Analog Output.
Current
(mA)
Illustration 3.10 Output
Maximum Scale
6-96 Terminal 42 Output Bus Control
Range:
Function:
0
[0 - 16384 ]
Hold the analog output at terminal
*
42 if controlled by bus.
3.8 Main Menu - Communications and
Options - Group 8
3.8.1 8-0* General Settings
8-01 Control Site
This parameter overrules settings in parameter 8-50 Coasting
Select to parameter 8-56 Preset Reference Select.
Option:
Function:
[0]
Digital and
Control by using both digital input
*
ctrl.word
and control word.
[1]
Digital only
Control by using digital inputs only.
[2]
Controlword
Control by using control word only.
only
20
0/4
0%
Analog
Analog
Variable
100%
output
Output
for
Min Scale
Max Scale
output
par. 6-93
par. 6-94
example:
Power
MG18P202