Saving settings and transferring them using an operator panel

You can transfer the inverter settings to the Operator Panel BOP-2 or vice versa, the data
from the BOP-2 to the inverter.
Precondition
The inverter power supply has been switched on.
Inverter → BOP-2
Procedure
To back up the settings on the BOP-2, proceed as follows:
1.
2.
3.
4.
You have backed up the settings on the BOP-2.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
7.3 Saving settings and transferring them using an operator panel
Go to the menu level "OPTIONS".
In the "OPTIONS" menu, select "TO BOP".
Start data transfer with OK.
Wait until the inverter has backed up the settings to the BOP-2.
Backing up data and series commissioning
367