On the right side of the SKF Multilog WVT unit, press the LCD display push button
and look for the message <IR> in the bottom banner of the unit's display.
Then, aim the PDA's IrDA port toward the SKF Multilog WVT display at a distance of
no more than 15 cm (6 in.).
Tap the option Reset Device to Defaults to prepare the device to be initialized by
the DataController software. (Resetting takes about five seconds.)
Next, tap the option Provision a Device to start the process. One of the keys loaded
into the PDA (in this example there are 15 keys) will be used to authenticate the
SKF Multilog WVT unit. Wait until the screen displays the message Device
provisioned successfully. Alternatively, a fail message will appear with an
explanation of why the process failed.
Tap OK to accept the message.
SKF Multilog On-line System WVT
User Manual
Figure 10 - 8.
Provisioning Menu Screen.
IrDA port
Figure 10 - 9.
PDA IrDA Ports.
Provisioning the Network Devices
Handheld Device Provisioning Method