YASKAWA Z1000U Series Programming Manual page 157

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

Setting 0: Legacy Operation Mode
When S5-04 = 0 (Legacy operation mode), the HAND/OFF/AUTO functionality for both the HOA keypad and multifunction
inputs.
Setting 1: Normal Operation Mode
When S5-04 = 1 (Normal operation mode), the functionality is as follows:
• AUTO mode: Drive frequency reference and run command are based on b1-01/b1-02.
• OFF mode: Drive is stopped and cannot run (except via Emergency Override multi-function input). Frequency reference is
based on b1-01.
• HAND mode: Drive runs at frequency reference selected via S5-01.
The AUTO, OFF and HAND states are selected either via the HOA keypad or multi-function inputs.
Parameter S5-01 selects the HAND mode frequency reference source. When S5-01 is set to 2, d1-16 is used as the HAND
mode reference. When S5-01 is set to 3, S5-05 is used. When S5-01 is set to 4, the frequency reference selected via b1-01 is
used as the HAND mode reference.
The only difference between d1-16 and S5-05 is that the unit for d1-16 changes based on o1-03, o1-10 and o1-11. However,
the unit for S5-05 is fixed at Hz.
Parameter S5-03 selects whether PID control is enabled or disabled in HAND mode.
Note:
The drive will always be in AUTO mode at power up with S5-04 = 1.
Table 1.34 HAND/AUTO Multi-Function Inputs, Standard Behavior (S5-04 = 1 or 2)
AUTO Mode Selection
HAND Mode Selection
(H1-oo = 6D)
Open
Open
Closed
Closed
When the AUTO and HAND multi-function inputs (setting 6D and 6E) are used, the HAND and AUTO keys on the HOA
keypad do not function.
If S5-04 is set to 1 or 2, the AUTO and HAND multi-function inputs (setting 6D and 6E) can only be used together or an
oPE03 error will occur.
S5-02 = 1 AND
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Operation Mode
(H1-oo = 6E)
Open
Closed
Open
Closed
S5-02 = 1 AND
HAND key
AUTO key
Figure 1.86 Standard Behavior (S5-04 = 1 or 2)
Frequency Reference
OFF
Based on b1-01
HAND
Based on S5-01
AUTO
Based on b1-01
OFF
Based on b1-01
AUTO
OFF key
Fref
via b1-01
Run
via b1-02
AUTO key
HAND key
HAND
Fref
via S5-01
Run
On
1.11 S: Special Parameters
Run Command
OFF
OFF
Based on b1-02
OFF
OFF
Fref
via b1-01
Run
Off
OFF key
1
157