A.9 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
70
Drive Enable2
A4
BP Customer Safeties
A5
BP Drive/Bypass Select BP Drv/Bypss Sel
A6
BP BAS Interlock Input BP BAS Interlock
A7
BP Customer Safeties
Secondary PI Disable
A8
(N.O.)
Secondary PI Disable
A9
(N.C.)
Secondary PI Inverse
AA
Operation
Secondary PI Integral
AB
Reset
Secondary PI Integral
AC
Hold
Select Secondary PI
AD
Parameters
AE
BP Bypass Run
Emergency Override
AF
Forward Run
Emergency Override
B0
Reverse Run
B1
Customer Safeties
B2
BAS Interlock
220
H1 Multi-Function Digital Input Selections
LCD Display
Prevents the Drive from executing a Run command until the Drive Enable2 input
is closed.
When the Drive Enable2 input is open and a Run command is closed, the drive
Drive Enable 2
LCD will display "dnE".
The drive will run when the Run and Drive Enable2 inputs are both closed. If the
Drive Enable2 input is opened while the drive is running, the drive will stop using
the method set by parameter b1-03.
BP Emg Override
Closed: Indicates that customer safeties are in place.
Open: Bypass mode.
Closed: Drive mode.
Closed: Indicates that the dampers are open
BP Cust Safeties
Closed: Indicates that customer safeties are in place.
Closed: Disables the secondary PI controller. Output behavior depends on the
PI2 Disable N.O.
setting of S3-12.
Closed: Enables the secondary PI controller. Output behavior depends on the
PI2 Disable N.C.
setting of S3-12 when open.
Closed: Changes the sign of the secondary PI controller input (reverse acting PID
PI2 Invert
control).
PI2 Intgrl Reset
Closed: Resets the secondary PI controller integral value.
PI2 Intgrl Hold
Closed: Locks the value of the secondary PI controller integral value.
Closed: Uses the secondary PI controller Proportional and Integral adjustments
(S3-06 and S3-07) instead of the primary PID controller Proportional and Integral
adjustments (b5-02 and b5-03). Only valid when S3-01 = 0 (secondary PI
Select PI2 Parms
controller disabled).
Note:
Closed: Commands a Run (via closing the BP Bypass Relay multi-function output)
BP Bypass Run
when in Bypass mode.
EmergOverrideFWD Closed: Emergency Override Forward Run
EmergOverrideREV
Closed: Emergency Override Reverse Run
The functionality is identical to Drive Enable 2 (H1-oo = 70), except for the
following characteristics:
• The stopping method is forced to Coast to Stop when the input is open
• The drive will display a "SAFE" alarm if the input is open when a Run command
CustomerSafeties
is present. It will not display "dnE".
Open: Customer Safeties are open. Drive will not run. Stopping method is Coast
to Stop.
Closed: Customer Safeties are in place.
Open: Damper interlock is not closed. Drive output is shut off (baseblocked). The
drive displays an "inTLK" message if a Run command is present. It will not display
"dnE".
Closed: Damper interlock is closed. Drive operates normally.
BAS Interlock
Note:
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Description
This multi-function input has no effect on the secondary PI
controller. It is only used for the primary PID controller (b5-oo).
The state of the BAS Interlock multi-function input has no effect on
the Emergency Override multi-function inputs (H1-oo = AF, B0).
The Emergency Override command is accepted when the BAS
Interlock digital input is open or closed.
Page
86
86
86
86
86
86
87
87
87
87
87
87
87
87
87
87