E2: Motor 1 Parameters; E5: Pm Motor Settings - YASKAWA Z1000U Series Programming Manual

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

A.7 E: Motor Parameters
<4> Default setting is dependent on parameter A1-02, Control Mode Selection.
<5> Values shown are specific to 200 V class drives. Double the value for 400 V class drives.
<6> Parameter ignored when E1-11 (Motor 1 Mid Output Frequency 2) and E1-12 (Motor 1 Mid Output Frequency Voltage 2) are set to 0.0.
<7> When Auto-Tuning is performed, E1-13 and E1-05 will be set to the same value.
<8> When using PM motors, the default setting is determined by the motor code set to E5-01.
<9> The drive changes these settings when Auto-Tuning is performed.
u

E2: Motor 1 Parameters

No.
(Addr.
Name
Hex)
E2-01
Motor Rated Current
(030E)
E2-02
Motor Rated Slip
(030F)
E2-03
Motor No-Load Current No-Load Current
(0310)
E2-04
Number of Motor Poles Number of Poles
(0311)
E2-05
Motor Line-to-Line
(0312)
Resistance
E2-10
Motor Iron Loss for
(0317)
Torque Compensation
E2-11
Motor Rated Power
(0318)
<1> Default setting is dependent on parameter o2-04, Drive Model Selection.
<2> Display is in the following units:
2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units
u

E5: PM Motor Settings

No.
(Addr.
Name
Hex)
E5-01
Motor Code Selection
(0329)
(for PM Motors)
<1>
E5-02
Motor Rated Power (for
(032A)
PM Motors)
<1>
208
LCD Display
Sets the motor nameplate full load current in amps.
Automatically set during Auto-Tuning.
Motor Rated FLA
Sets the motor rated slip. Automatically set during
Auto-Tuning.
Motor Rated Slip
Sets the no-load current for the motor. Automatically set during
Auto-Tuning.
Sets the number of motor poles. Automatically set during
Auto-Tuning.
Sets the phase-to-phase motor resistance. Automatically set
during Auto-Tuning.
Term Resistance
Sets the motor iron loss.
Motor Iron Loss
Sets the motor rated power in kilowatts (1 HP = 0.746 kW).
Automatically set during Auto-Tuning.
Mtr Rated Power
LCD Display
OLV/PM
OLV/PM
Enter the Yaskawa motor code for the PM motor being used.
Various motor parameters are automatically set based on the
value of this parameter. Settings that were changed manually
will be overwritten by the defaults of the selected motor code.
PM Mtr Code Sel
Note:
OLV/PM
OLV/PM
PM Mtr Capacity
Sets the rated capacity of the motor.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Description
Description
1. Set to FFFF when using a non-Yaskawa PM
motor or a special motor.
2. If an alarm or hunting occurs despite using a
motor code, enter the value indicated on the
nameplate.
Values
Page
<1>
Default:
Min.: 10% of
drive rated
current
62
Max.: 150% of
drive rated
<2>
current
<1>
Default:
62
Min.: 0.00 Hz
Max.: 20.00 Hz
<1>
Default:
Min.: 0.00 A
62
<2>
Max.: E2-01
Default: 4
Min.: 2
63
Max.: 48
<1>
Default:
63
Min.: 0.000 Ω
Max.: 65.000 Ω
<1>
Default:
63
Min.: 0 W
Max.: 65535 W
<1>
Default:
63
Min.: 0.00 kW
Max.: 650.00 kW
Values
Page
<2>
Default:
Min.: 0000
64
<4>
Max.: FFFF
<3>
Default:
64
Min.: 0.10 kW
Max.: 650.00 kW