YASKAWA Z1000U Series Programming Manual page 131

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

n
n8-45: Speed Feedback Detection Control Gain (OLV/PM)
Sets the gain for internal speed feedback detection control. Although this parameter rarely needs to be changed, adjustment
may be necessary under the following conditions:
• Increase this setting if motor oscillation or hunting occurs.
• Decrease this setting in increments of 0.05 to decrease drive responsiveness.
No.
n8-45
n
n8-47: Pull-In Current Compensation Time Constant (OLV/PM)
Sets the time constant for pull-in current to match the actual current.
Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions:
• Increase this setting when it takes too long for the reference value of the pull-in current to match the target value.
• Decrease this setting if motor oscillation occurs.
No.
n8-47
n
n8-48: Pull-In Current (OLV/PM)
Sets the d-Axis current during no-load operation at a constant speed. Set as a percentage of the motor rated current.
• Increase this setting when hunting occurs or the motor speed is unstable while running at a constant speed.
• Slightly reduce this value if there is too much current when driving a light load at a constant speed.
No.
n8-48
n
n8-49: d-Axis Current for High Efficiency Control (OLV/PM)
Sets the d-Axis current reference when running with high load at constant speed. When using an IPM motor, this parameter
uses the reluctance torque to increase the efficiency and reduce energy consumption. Set this parameter to 0 when using an
SPM motor.
Although this setting rarely needs to be changed, adjustment may be necessary under the following conditions:
• Lower the setting if motor operation is unstable when driving heavy loads.
• If motor parameters (E5-oo) have been changed, this value will be reset to 0 and will require readjustment.
No.
n8-49
n
n8-51: Acceleration/Deceleration Pull-In Current (OLV/PM)
Sets the pull-in current during acceleration and deceleration as a percentage of the motor rated current (E5-03).
Adjustment may be necessary under the following conditions:
• Increase this setting when a large amount of starting torque is required.
• Lower this setting if there is excessive current during acceleration.
No.
n8-51
n
n8-54: Voltage Error Compensation Time Constant (OLV/PM)
Sets the time constant for voltage error compensation.
Adjustment may be necessary under the following conditions:
• Adjust the value when hunting occurs at low speed.
• Increase the value in steps of 0.1 when hunting occurs with sudden load changes. Set n8-51 to 0 to disable the compensation
if increasing n8-54 does not help.
• Increase the value when oscillations occur at start.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Name
Speed Feedback Detection Control Gain
Name
Pull-In Current Compensation Time Constant
Name
Pull-In Current
Name
d Axis Current for High Efficiency Control
Name
Acceleration/Deceleration Pull-In Current
1.9 n: Special Adjustments
Setting Range
0.00 to 10.00
Setting Range
0.0 to 100.0 s
Setting Range
20 to 200%
Setting Range
Determined by
-200.0 to 0.0%
Setting Range
0 to 200%
Default
0.80
Default
5.0 s
Default
30%
Default
o2-04
Default
50%
1
131

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000 cimr-zu series

Table of Contents