YASKAWA Z1000U Series Programming Manual page 88

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

1.7 H: Terminal Functions
Setting
6
Drive Ready
7
During Power Supply Voltage Fault
8
During Baseblock (N.O.)
9
Frequency Reference Source
A
Run Command Source
B
Torque Detection 1 (N.O.)
C
Frequency Reference Loss
E
Fault
F
Through Mode
10
Minor Fault
11
Fault Reset Command Active
12
Timer Output
13
Speed Agree 2
14
User-Set Speed Agree 2
15
Frequency Detection 3
16
Frequency Detection 4
17
Torque Detection 1 (N.C.)
1B
During Baseblock (N.C.)
1E
Restart Enabled
1F
Motor Overload Alarm (oL1)
20
Drive Overheat Pre-Alarm (oH)
2F
Maintenance Period
37
During Frequency Output
38
Drive Enabled
39
Power Consumption Pulse Output
Setting 0: During Run
Output closes when the drive is outputting a voltage.
Status
Open
Drive is stopped.
Closed
A Run command is input or the drive is in deceleration or DC injection.
Setting 1: Zero Speed
Terminal closes when the output frequency falls below the minimum output frequency set to E1-09 or b2-01.
Status
Open
Output frequency is above the minimum output frequency set to E1-09 or b2-01
Closed
Output frequency is less than the minimum output frequency set to E1-09 or b2-01
88
Function
OFF
ON
Run command
Baseblock
OFF
command
Output
frequency
OFF
ON
During Run
Figure 1.40 During Run Time Chart
Page
Setting
91
3A
Regenerated Power Pulse Output
91
3D
During Speed Search
91
3E
PID Feedback Low
91
3F
PID Feedback High
91
4C
During Fast Stop
92
4D
oH Pre-Alarm Time Limit
92
50
Waiting for Run
92
51
Sequence Timer 1 Active
92
52
Sequence Timer 2 Active
92
53
Sequence Timer 3 Active
92
54
Sequence Timer 41 Active
92
58
Underload Detection
92
60
Internal Cooling Fan Alarm
93
62
MEMOBUS Register 1
93
63
MEMOBUS Register 2
94
64
During Commercial Power Operation
92
AF
BP Drive Relay Contact
94
B0
BP Bypass Relay Contact
94
B1
BP BAS Interlock Relay Contact
94
B2
BAS Interlock Relay Contact
95
B3
Secondary PI Feedback Low
95
B4
Secondary PI Feedback High
95
B5
Relay Operator Control
95
B6
Drive Overheat Alarm 2
95
100 to 1B6 Functions 0 to B6 with Inverse Output
Description
ON
Description
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Function
Page
95
95
95
95
95
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
96
97
97
97