YASKAWA Z1000U Series Programming Manual page 59

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

Predefined V/f Patterns for Models 4o0011 and 4o0014
Setting = 0
50 Hz
400
30
18
0
1.3 2.5
50
Frequency (Hz)
Setting = 4
50 Hz
400
70
16
0
1.3
25
50
Frequency (Hz)
Setting = 8
50 Hz
400
38
22
0
1.3 2.5
50
Frequency (Hz)
Setting = C
90 Hz
400
30
18
0
1.5 3
60
90
Frequency (Hz)
Predefined V/f Patterns for Models 2o0028 to 2o0192 and 4o0021 to 4o0124
The values in the following graphs are specific to 200 V class drives. Double the values for 400 V class drives.
Setting = 0
50 Hz
200
14
7
0
1.3 2.5
50
Frequency (Hz)
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Table 1.19 Constant Torque Characteristics, Settings 0 to 3
Setting = 1
60 Hz
400
30
18
0
1.5 3
60
Frequency (Hz)
Table 1.20 Derated Torque Characteristics, Settings 4 to 7
Setting = 5
50 Hz
400
100
18
0
1.3
25
50
Frequency (Hz)
Table 1.21 High Starting Torque, Settings 8 to B
Setting = 9
50 Hz
400
48
26
0
1.3 2.5
50
Frequency (Hz)
Table 1.22 Rated Output Operation, Settings C to F
Setting = D
120 Hz
400
30
18
0
1.5 3
60
120
Frequency (Hz)
Table 1.23 Rated Torque Characteristics, Settings 0 to 3
Setting = 1
60 Hz
200
14
7
0
1.5 3
60
Frequency (Hz)
Setting = 2
60 Hz
400
30
18
0
1.5 3
50
60
Frequency (Hz)
Setting = 6
60 Hz
400
70
16
0
1.5
30
60
Frequency (Hz)
Setting = A
60 Hz
400
38
22
0
1.5 3
60
Frequency (Hz)
Setting = E
180 Hz
400
30
18
0
1.5 3
60
180
Frequency (Hz)
Setting = 2
60 Hz
200
14
7
0
1.5 3
50
60
Frequency (Hz)
1.5 E: Motor Parameters
Setting = 3
72 Hz
400
30
18
0
1.5 3
60
72
Frequency (Hz)
Setting = 7
60 Hz
400
100
18
0
1.5
30
60
Frequency (Hz)
Setting = B
60 Hz
400
48
30
0
1.5 3
60
Frequency (Hz)
Setting = F
60 Hz
400
30
18
0
1.5 3
60
Frequency (Hz)
Setting = 3
72 Hz
200
14
7
0
1.5 3
60
72
Frequency (Hz)
1
59

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000 cimr-zu series

Table of Contents