A.9 H Parameters: Multi-Function Terminals
No.
(Addr.
Name
Hex)
H3-10
Terminal A2 Function
(0418)
Selection
H3-11
Terminal A2 Gain
(0419)
Setting
H3-12
(041A) Terminal A2 Bias
Setting
H3-13
Analog Input Filter Time
(041B)
Constant
H3-14
Analog Input Terminal
(041C)
Enable Selection
H3-16
Terminal A1 Offset
(02F0)
H3-17
Terminal A2 Offset
(02F1)
H3-18
Terminal A3 Offset
(02F2)
<1> Default is 0 when b5-01 is set to 0.
Default is B when b5-01 is set to 1 or 3.
H3-oo
Function
Setting
0
Frequency bias
1
Frequency gain
Auxiliary frequency
reference 1
2
(used as a Multi-Step
Speed 2)
Auxiliary frequency
3
reference 2
(3rd step analog)
4
Output voltage bias
5
Accel/decel time gain
DC Injection Braking
6
current
Overtorque/undertorque
7
detection level
Stall Prevention level
8
during run
Output frequency lower
9
limit level
B
PID feedback
C
PID setpoint
224
LCD Display
Sets the function of terminal A2.
Term A2 FuncSel
Sets the level of the input value selected in H3-10 when 10 V
(20 mA) is input at terminal A2.
Terminal A2 Gain
Sets the level of the input value selected in H3-10 when 0 V (0
or 4 mA) is input at terminal A2.
Terminal A2 Bias
Sets a primary delay filter time constant for terminals A1 and
A1/A2 Filter T
A2. Used for noise filtering.
Determines which analog input terminals will be enabled or
disabled when a digital input programmed for "Analog input
A1/A2/A3 Sel
enable" (H1-oo = C) is activated.
1: A1 Available
The terminals not set as the target are not influenced by input
2: A2 Available
signals.
3: A1/A2 Available
1: Terminal A1 only
4: A3 Available
2: Terminal A2 only
5: A1/A3 Available
3: Terminals A1 and A2 only
6: A2/A3 Available
4: Terminal A3 only
7: All Available
5: Terminals A1 and A3
6: Terminals A2 and A3
7: All terminals enabled
Adds an offset when the analog signal to terminal A1 is at 0 V. Default: 0
TerminalA1Offset
Adds an offset when the analog signal to terminal A2 is at 0 V. Default: 0
TerminalA2Offset
TerminalA3Offset
Adds an offset when the analog signal to terminal A3 is at 0 V.
H3 Multi-Function Analog Input Settings
LCD Display
Freq Ref Bias
10 V = E1-04 (maximum output frequency)
0 to 10 V signal allows a setting of 0 to 100%. -10 to 0 V signal allows a setting
Freq Ref Gain
of -100 to 0%.
10 V = E1-04 (maximum output frequency)
Aux Reference1
10 V = E1-04 (maximum output frequency)
Aux Reference2
Voltage Bias
10 V = E1-05 (motor rated voltage)
Acc/Dec Change
10 V = 100%
10 V = Drive rated current
DC Brake Current
10 V = Drive rated current (V/f)
Torque Det Level
10 V = Motor rated torque (OLV/PM)
10 V = Drive rated current
Stall Prev Level
10 V = E1-04 (maximum output frequency)
Ref Lower Limit
PID Feedback1
10 V = 100%
PID Set Point
10 V = 100%
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Description
Description
Values
Page
<1>
Default:
100
Range: 0 to 26
Default: 100.0%
Min.: -999.9
100
Max.: 999.9
Default: 0.0%
Min.: -999.9
100
Max.: 999.9
Default: 0.03 s
Min.: 0.00
100
Max.: 2.00
Default: 7
101
Range: 1 to 7
Min.: -500
101
Max.: 500
Min.: -500
101
Max.: 500
Default: 0
Min.: -500
101
Max.: 500
Page
101
101
102
102
102
102
102
102
102
103
103
103