S3-13
PI2 Low Feedback
Detection Level
S3-15
PI2 High Feedback
Detection Level
n
S3-14: Secondary PI Low Feedback Detection Time
Sets the secondary PI low feedback detection delay time in seconds.
No.
S3-14
n
S3-15: Secondary PI High Feedback Level
Sets the secondary PI high feedback detection level.
No.
S3-15
<1> Upper limit is S3-02, decimal place holder is determined by S3-03.
<2> Unit is determined by S3-04.
n
S3-16: Secondary PI High Feedback Detection Time
Sets the secondary PI high feedback detection delay time in seconds.
No.
S3-16
n
S3-17: Secondary PI Feedback Detection Selection
Selects when secondary PI controller low and high feedback detection is active.
No.
S3-17
Setting 0: Secondary PI Enabled
Setting 1: Always
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
PI2 Feedback
(U5-18)
+
-
+
-
Figure 1.80 PI Low Feedback Detection Level
Name
Secondary PI Low Feedback Detection Time
Name
Secondary PI High Feedback Level
Name
Secondary PI High Feedback Detection Time
Name
Secondary PI Feedback Detection Selection
PI2 disabled
S3-17 = 0
S3-14
PI2 Low Feedback
Detection Time
False
On-delay
Timer
True
S3-16
PI2 High Feedback
Detection Time
False
On-delay
Timer
True
1.11 S: Special Parameters
Multi-function output
H2-oo = 71
PI2 Feedback Low
Multi-function output
H2-oo = 72
PI2 Feedback Low
Setting Range
0.0 to 25.5 s
Setting Range
<1>
0.00 to 600.00
Setting Range
0.0 to 25.5 s
Setting Range
0 or 1
Default
1.0 s
Default
<2>
300.0
Default
1.0 s
Default
0
1
149