YASKAWA Z1000U Series Programming Manual page 75

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

n
F6-50: DeviceNet MAC Address
Sets the MAC address for a DeviceNet option card.
No.
F6-50
n
F6-51: DeviceNet Communication Speed
Sets the communication speed for a DeviceNet option card.
To assign the baud rate for the drive from the upper controller, set F6-51 = 3.
To make the drive detect the network speed, set F6-51 = 4. The drive will automatically adjust itself after detecting the network
speed.
No.
F6-51
Setting 0: 125 kbps
Setting 1: 250 kbps
Setting 2: 500 kbps
Setting 3: Adjustable from network
Setting 4: Auto detection
n
F6-52: DeviceNet PCA Setting
Defines the format for data the drive receives from the DeviceNet master.
No.
F6-52
n
F6-53: DeviceNet PPA Setting
Defines the format for data sent from the drive to the DeviceNet master.
No.
F6-53
n
F6-54: DeviceNet Idle Mode Fault Detection
Determines whether the drive triggers an EF0 fault when no data is received from the master (e.g., when the master is idling).
No.
F6-54
Setting 0: Enabled
Setting 1: Disabled, No Fault Detection
n
F6-55: DeviceNet Baud Rate Monitor
Displays the baud rate currently being used for network communications. F6-55 is used only as a monitor.
No.
F6-55
Setting 0: 125 kbps
Setting 1: 250 kbps
Setting 2: 500 kbps
n
F6-56 to F6-61: DeviceNet Scaling Factors
These parameters define scaling factors for drive monitors in the DeviceNet Class ID 2AH - AC/DC Drive Object.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Parameter Name
DeviceNet MAC Address
Parameter Name
DeviceNet Communication Speed
Parameter Name
DeviceNet PCA Setting
Parameter Name
DeviceNet PPA Setting
Parameter Name
DeviceNet Idle Mode Fault Detection
Parameter Name
DeviceNet Baud Rate Monitor
1.6 F: Option Settings
Setting Range
0 to 64
Setting Range
0 to 4
Setting Range
0 to 255
Setting Range
0 to 255
Setting Range
0, 1
Setting Range
0 to 2 (read only)
Default
64
Default
4
Default
21
Default
71
Default
0
Default
0
1
75