YASKAWA Z1000U Series Programming Manual page 212

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

A.8 F: Option Settings
No.
(Addr.
Name
Hex)
External Fault from
F6-03
Comm. Option
(03A4)
Operation Selection
F6-04
bUS Error Detection
(03A5)
Time
Torque Reference/
F6-06
Torque Limit Selection
(03A7)
from Comm. Option
Multi-Step Speed
F6-07
Enable/Disable
(03A8)
Selection when NefRef/
ComRef is Selected
F6-08
Reset Communication
(036A)
Parameters
<3>
F6-10
CC-Link Node Address CC-Link Node Add
(03B6)
F6-11
CC-Link
(03B7)
Communication Speed
F6-14
CC-Link bUS Error
(03BB)
Auto Reset
F6-20
MECHATROLINK
(036B)
Station Address
F6-21
MECHATROLINK
(036C)
Frame Size
F6-22
MECHATROLINK
(036D)
Link Speed
F6-23
MECHATROLINK
(036E)
Monitor Selection (E)
F6-24
MECHATROLINK
(036F)
Monitor Selection (F)
Operation Selection at
F6-25
MECHATROLINK
(03C9)
Watchdog Timer Error
(E5)
F6-26
MECHATROLINK
(03CA)
bUS Errors Detected
F6-30
PROFIBUS-DP Node
(03CB)
Address
F6-31
PROFIBUS-DP Clear
(03CC)
Mode Selection
212
LCD Display
0: Ramp to stop. Decelerate to stop using the deceleration time
EF0 Fault Action
in C1-02.
0: Ramp to Stop
1: Coast to stop.
1: Coast to Stop
2: Fast Stop. Decelerate to stop using the deceleration time in
2: Fast-Stop
C1-09.
3: Alarm Only
3: Alarm only.
BUS Err Det Time
Sets the delay time for error detection if a bus error occurs.
Torq Ref/Lmt Sel
OLV/PM
OLV/PM
0: Disabled
0: Disabled. Torque reference/limit from option board disabled.
1: Enabled
1: Enabled. Torque reference/limit from option board enabled.
0: Multi-step reference disabled (same as F7)
Fref PrioritySel
1: Multi-step reference enabled (same as V7)
0: Net/Com REF
1: MultiStep Speed
0: Communication-related parameters (F6-oo) are not reset
Com Prm Init Sel
when the drive is initialized using A1-03.
0: No Init Com Prms
1: Reset all communication-related parameters (F6-oo) when
1: Init Com Prms
the drive is initialized using A1-03.
Sets the node address if a CC-Link option is installed.
CC-Link Baud
0: 156 Kbps
0: 156 kbps
1: 625 Kbps
1: 625 kbps
2: 2.5 Mbps
2: 2.5 Mbps
3: 5 Mbps
3: 5 Mbps
4: 10 Mbps
4: 10 Mbps
Bus Err Auto Rst
0: Disabled
0: Disabled
1: Enabled
1: Enabled
Sets the station address when the MECHATROLINK option
Station Address
has been installed.
MECHATROLINK-II (SI-T3)
0: 32-byte
1: 17-byte
Frame length
MECHATROLINK-III (SI-ET3)
0: 64-byte
1: 32-byte
Link Speed
0: 10 Mbps
0: 10MHz
1: 4 Mbps
1: 4MHz
Mon E register
Sets the MECHATROLINK monitor (E).
Mon F register
Sets the MECHATROLINK monitor (F).
SI-T WDTErr Sel
0: Ramp to stop. Decelerate using the deceleration time in
0: Ramp to Stop
C1-02.
1: Coast to Stop
1: Coast to stop
2: Fast-Stop
2: Fast stop. Decelerate using the deceleration time in C1-09.
3: Alarm Only
3: Alarm only
Num of SI-T BUS
Sets the number of option communication errors (bUS).
PB Node Address
Sets the node address.
PB Clear Select
0: Resets drive operation with a Clear mode command.
0: Reset to Zero
1: Maintains the previous operation state when Clear mode
1: Hold Prev Value
command is given.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Description
<1>
Values
Page
Default: 1
70
Range: 0 to 3
Default: 2.0 s
Min.: 0.0
71
Max.: 5.0
Default: 0
70
Range: 0, 1
Default: 0
70
Range: 0, 1
Default: 0
71
Range: 0, 1
Default: 0
Min.: 0
71
Max.: 64
Default: 0
71
Range: 0 to 4
Default: 0
71
Range: 0, 1
Default: 21
<2>
Min.: 20
71
<2>
Max.: 3F
Default: 0
72
Range: 0, 1
Default: 0
72
Range: 0, 1
Default: 0
Min.: 0
72
Max.: FFFF
Default: 0
Min.: 0
72
Max.: FFFF
Default: 1
72
Range: 0 to 3
Default: 2
Min.: 2
73
Max.: 10
Default: 0
Min.: 0
73
Max.: 125
Default: 0
73
Range: 0, 1