1.12 T: Motor Tuning
n
T2-05: PM Motor Rated Voltage
Sets the motor rated voltage.
No.
T2-05
<1> Value shown is specific to 200 V class drives. Double value for 400 V class drives.
n
T2-06: PM Motor Rated Current
Enter the motor rated current in amps.
No.
T2-06
n
T2-07: PM Motor Base Frequency
Enter the motor base frequency in Hz.
Note:
T2-07 will be displayed when in OLV/PM.
No.
T2-07
n
T2-08: Number of PM Motor Poles
Enter the number of motor poles.
No.
T2-08
n
T2-10: PM Motor Stator Resistance
Enter the motor stator resistance per motor phase.
No.
T2-10
n
T2-11: PM Motor d-Axis Inductance
Enter the d-Axis inductance per motor phase.
No.
T2-11
n
T2-12: PM Motor q-Axis Inductance
Enter the q-Axis inductance per motor phase.
No.
T2-12
n
T2-13: Induced Voltage Constant Unit Selection
Selects the units used for setting the induced voltage coefficient.
No.
T2-13
Setting 0: mV (r/min)
Setting 1: mV (rad/sec)
Note:
If T2-13 is set to 0, then the drive will use E5-24 (Motor Induction Voltage Constant 2), and will automatically set E5-09 (Motor Induction
Voltage Constant 1 (Ke)) to 0.0. If T2-13 is set to 1, then the drive will use E5-09 and will automatically set E5-25 to 0.0.
162
Name
PM Motor Rated Voltage
Name
PM Motor Rated Current
Name
PM Motor Base Frequency
Name
Number of PM Motor Poles
Name
PM Motor Stator Resistance
Name
PM Motor d-Axis Inductance
Name
PM Motor q-Axis Inductance
Name
Induced Voltage Constant Unit Selection
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Setting Range
<1>
0.0 to 255.0 V
Setting Range
0.0% to 300.0% of the
Determined by o2-04
drive rated current.
Setting Range
0.0 to 400.0 Hz
Setting Range
2 to 48
Setting Range
0.000 to 65.000 Ω
Determined by T2-02
Setting Range
0.00 to 600.00 mH
Determined by T2-02
Setting Range
0.00 to 600.00 mH
Determined by T2-02
Setting Range
0, 1
Default
<1>
200.0 V
Default
Default
87.5 Hz
Default
6
Default
Default
Default
Default
1