YASKAWA Z1000U Series Programming Manual page 219

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

H1-oo
Function
Setting
31
PID integral hold
34
PID soft starter cancel
35
PID input level selection PID Input Invert
Forward run command
40
(2-Wire sequence)
Reverse run command
41
(2-Wire sequence)
Run command
42
(2-Wire sequence 2)
FWD/REV command
43
(2-Wire sequence 2)
44
Offset frequency 1
45
Offset frequency 2
46
Offset frequency 3
47
Node setup
50
Motor Pre-Heat 2
51
Sequence Timer Disable SeqTimer Disable
52
Sequence Timer Cancel
60
Motor pre-heat 1
External Speed Search
61
command 1
External Speed Search
62
command 2
63
Field weakening
Communications test
67
mode
69
Jog 2
6A
Drive enable
6D
AUTO mode select
6E
HAND mode select
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
H1 Multi-Function Digital Input Selections
LCD Display
Open: Performs integral operation.
PID Intgrl Hold
Closed: Maintains the current PID control integral value.
Open: PID soft starter is enabled.
PID SFS Cancel
Closed: Disables the PID soft starter b5-17.
Closed: Inverts the PID input signal.
Open: Stop
Closed: Forward run
FwdRun 2Wire Seq
Note:
Open: Stop
Closed: Reverse run
RevRun 2WireSeq
Note:
Open: Stop
Closed: Run
Run/Stp 2WireSeq
Note:
Open: Forward
Closed: Reverse
FWD/REV 2WireSeq
Note:
Offset Freq 1
Closed: Adds d7-01 to the frequency reference.
Offset Freq 2
Closed: Adds d7-02 to the frequency reference.
Offset Freq 3
Closed: Adds d7-03 to the frequency reference.
CanOpenNID Setup
Closed: Node setup for SI-S3 enabled.
Motor Preheat 2
Closed: Triggers Motor Pre-Heat 2.
Closed: Drive ignores sequence timers and runs normally.
SeqTimer Cancel
Closed: Sequence Timer Cancel .
DCInj Activate
Closed: Triggers Motor pre-heat 1.
Closed: Activates Current Detection Speed Search from the maximum output
Speed Search 1
frequency (E1-04).
Speed Search 2
Closed: Activates Current Detection Speed Search from the frequency reference.
Field Weak
Closed: The drive performs Field Weakening control as set for d6-01 and d6-02.
Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays "PASS" if the
Comm Test Mode
test completes successfully.
Jog 2
Cause the drive to ramp to the jog frequency (d1-17).
Open: Drive disabled. If this input is opened during run, the drive will stop as
Drive Enable
specified by b1-03.
Closed: Ready for operation.
Legacy Operation Mode (S5-04 = 0)
• Open: HAND reference is selected (based on S5-01)
• Closed: AUTO reference is selected (based on b1-01)
Normal Operation Mode (S5-04 ≠ 0)
AUTO Mode Sel
Note:
• Open: Drive is in OFF or HAND mode.
• Closed: Drive is in AUTO mode (when HAND mode select input is open)
Legacy Operation Mode (S5-04 = 0)
• Open: AUTO reference is selected (based on b1-01)
• Closed: HAND reference is selected (based on S5-01)
Normal Operation Mode (S5-04 ≠ 0)
HAND Mode Se
Note:
• Open: Drive is in OFF or AUTO mode.
• Closed: Drive is in HAND mode. (when AUTO mode select input is open)
A.9 H Parameters: Multi-Function Terminals
Description
Cannot be set together with settings 42 or 43.
Cannot be set together with settings 42 or 43.
Cannot be set together with settings 40 or 41.
Determines motor direction, but does not issue a Run command.
Cannot be set together with settings 40 or 41.
The drive will always be in AUTO mode at power up when
S5-04 is set to 1.
The drive will always be in AUTO mode at power up when
S5-04 is set to 1.
Page
84
84
84
84
84
84
84
85
85
85
85
85
85
85
85
85
85
85
85
85
86
86
86
A
219