Modbus Tcp/Ip Parameters; Profinet Parameters; Ethernet/Ip Parameters - YASKAWA Z1000U Series Programming Manual

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

1.6 F: Option Settings
No.
F6-56
F6-57
F6-58
F6-59
F6-60
F6-61
Setting
The monitor value in the AC/DC Drive Object 2AH is calculated by:
AC/DC Drive Object 2AH Monitor = Drive Value × 2
Example:
If the drive output frequency monitor (U1-02) is 5.00 and the scaling is set to F6-56 = 6, then the value in the AC/DC Drive
Object 2AH, Instance 1, Attribute 7 would be 500 × 2
n
F6-62: DeviceNet Heartbeat Interval
Sets the heartbeat interval for DeviceNet communications. A setting of 0 disables the heartbeat function.
No.
F6-62
n
F6-63: DeviceNet Network MAC ID
Displays the MAC ID assigned to the drive. F6-63 is used only as a monitor.
No.
F6-63
n
F6-64 to F6-71: Dynamic Assembly Parameters (Reserved)
n
F7-01 to F7-04: IP Address 1 to 4
Sets the significant octet of network static IP address.
n
F7-05 to F7-08: Subnet Mask 1 to 4
Sets the significant octet of network static Subnet Mask.
n
F7-09 to F7-12: Gateway Address 1 to 4
Sets the significant octet of network Gateway address.
u

Modbus TCP/IP Parameters

Parameters F7-01 through F7-16, U6-80 through U6-93, U6-98, and U6-99 set up the drive to operate on a Modbus TCP/IP
network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option Modbus TCP/IP Installation Manual
and Technical Manual.
u

PROFINET Parameters

Parameters F7-01 through F7-15, F7-17 through F7-42, U6-80 through U6-93, U6-98, and U6-99 set up the drive to operate
on a PROFINET network.
For details on parameter settings, refer to the YASKAWA AC Drive 1000-Series Option PROFINET Installation Manual and
Technical Manual.
u

EtherNet/IP Parameters

Parameters F7-01 through F7-15, F7-17 through F7-42, U6-80 through U6-93, U6-98, and U6-99 set up the drive to operate
on an EtherNet/IP network.
76
Parameter Name
DeviceNet Speed Scaling
DeviceNet Current Scaling
DeviceNet Torque Scaling
DeviceNet Power Scaling
DeviceNet Voltage Scaling
DeviceNet Time Scaling
Scaling
6
= 32000.
Parameter Name
DeviceNet Heartbeat Interval
Parameter Name
DeviceNet Network MAC ID
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Setting Range
-15 to 15
-15 to 15
-15 to 15
-15 to 15
-15 to 15
-15 to 15
Setting Range
0 to 10
Setting Range
0 to 63 (read only)
Default
0
0
0
0
0
0
Default
0
Default
63

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000 cimr-zu series

Table of Contents