Setting 20: Drive Overheat Pre-Alarm (oH)
The output closes when the drive heatsink temperature reaches the level specified by parameter L8-02.
Overheat Alarm Level on page 123
Setting 2F: Maintenance Period
The output closes when the cooling fan, capacitor for the control power supply, or DC bus pre-charge relay may require
maintenance as determined by the estimated performance life span of those components. Components performance life is
displayed as a percentage on the HOA keypad screen.
Setting 37: During Frequency Output
The output closes when the drive is outputting a frequency.
Status
Open
Drive is stopped or one of the following functions is being performed: baseblock, DC Injection Braking.
Closed
Drive is outputting frequency.
Setting 38: Drive Enable
Reflects the status of a digital input configured as a "Drive enable" input (H1-oo = 6A). If that digital input closes, then the
digital output set for "Drive enable" will also close.
Setting 39: Power Consumption Pulse Output
Outputs a pulse to indicate the watt hours.
Setting 3A: Regenerated Power Pulse Output
Outputs a pulse to indicate the regenerated power.
Setting 3D: During Speed Search
The output terminal closes while Speed Search is being performed.
Setting 3E: PID Feedback Low
The output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it falls below the
level set to b5-13 for longer than the time set to b5-14.
Setting 3F: PID Feedback High
The output terminal closes when a PID feedback loss is detected. The feedback is considered to be lost if it rises beyond the
level set to b5-36 for longer than the time set to b5-37.
Setting 4C: During Fast Stop
The output terminal closes when a Fast Stop is being executed.
82.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
for details on drive overheat detection.
OFF
ON
run command
baseblock
OFF
command
output
frequency
OFF
ON
during run
OFF
during frequency
output
Figure 1.50 During Frequency Output Time Chart
Description
ON
ON
Refer to b3: Speed Search on page 23
Refer to PID Feedback Loss Detection on page 36
Refer to PID Feedback Loss Detection on page 36
Refer to Settings 15 and 17: Fast Stop (N.O., N.C.) on page
1.7 H: Terminal Functions
Refer to L8-02:
for details.
for details.
for details.