YASKAWA Z1000U Series Programming Manual page 227

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

No.
(Addr.
Name
Hex)
Operation Selection
H5-17
when Unable to Write
(11A1)
into EEPROM
H5-18
Filter Time Constant for
(11A2)
Motor Speed Monitoring
<1> If this parameter is set to 0, the drive will be unable to respond to MEMOBUS/Modbus commands.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
LCD Display
Selects operation when an attempt is made to write data into
EEPROM via MEMOBUS/Modbus communications and
Busy Enter Sel
writing into EEPROM is not possible.
0: No ROM Enter
There is normally no need to change this parameter from the
1: RAM Enter
default value
0: Cannot write into EEPROM
1: Write in RAM only
Sets the filter time constant for monitoring the motor speed from
MEMOBUS/Modbus communications and communication
MtrSpd Monitor T
options.
Applicable MEMOBUS/Modbus registers are: 3EH, 3FH, 44H,
ACH, and ADH
A.9 H Parameters: Multi-Function Terminals
Description
Values
Page
Default: 0
287
Range: 0, 1
Default: 0 ms
Min.: 0
287
Max.: 100