YASKAWA Z1000U Series Programming Manual page 218

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

A.9 H Parameters: Multi-Function Terminals
H1-oo
Function
Setting
Drive overheat alarm
B
(oH2)
Analog terminal input
C
selection
F
Through mode
10
Up command
11
Down command
12
Forward Jog
13
Reverse Jog
14
Fault reset
15
Fast Stop (N.O.)
17
Fast Stop (N.C.)
18
Timer function input
19
PID disable
1B
Program lockout
1E
Reference sample hold
20 to 2F External fault
30
PID integral reset
218
H1 Multi-Function Digital Input Selections
LCD Display
OH2 Alarm Signal
Closed: Closes when an oH2 alarm occurs
Open: Function assigned by H3-14 is disabled.
Term A2 Enable
Closed: Function assigned by H3-14 is enabled.
Select this setting when using the terminal in a pass-through mode. The terminal
Term Not Used
does not trigger a drive function, but it can be used as digital input for the controller
to which the drive is connected.
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
Up Command 1
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
The drive accelerates when the Up command terminal closes, and decelerates when
the Down command closes. When both terminals are closed or both are open, the
Down Command 1
drive holds the frequency reference. The Up and Down commands must always
be used in conjunction with one another.
Forward Jog
Closed: Runs forward at the Jog frequency d1-17.
Reverse Jog
Closed: Runs reverse at the Jog frequency d1-17.
Fault Reset
Closed: Resets faults if the cause is cleared and the Run command is removed.
Fast-Stop N.O.
Closed: Decelerates at the Fast Stop time set to C1-09.
Fast-Stop N.C.
Open: Decelerates to stop at the Fast Stop time set to C1-09.
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in conjunction
Timer function
with the timer function output (H2-oo = 12).
Open: PID control enabled
PID Disable
Closed: PID control disabled
Open: Parameters cannot be edited (except for U1-01 if the reference source is
Program Lockout
assigned to the HOA keypad).
Closed: Parameters can be edited and saved.
Closed: Samples the analog frequency reference and operates the drive at that
Ref Sample Hold
speed.
External fault
20: NO/Always Det,
Ramp to Stop
21: NC/Always Det,
Ramp to Stop
22: NO/During RUN,
Ramp to Stop
23: N.C., During run,
ramp to stop
20: N.O., Always detected, ramp to stop
24: NO/ Always Det,
21: N.C., Always detected, ramp to stop
Coast to Stop
22: N.O., During run, ramp to stop
25: NC/Always Det,
23: N.C., During run, ramp to stop
Coast to Stop
24: N.O., Always detected, coast to stop
26: NO/During RUN,
25: N.C., Always detected, coast to stop
Coast to Stop
26: N.O., During run, coast to stop
27: NC/During RUN,
27: N.C., During run, coast to stop
Coast to Stop
28: N.O., Always detected, Fast Stop
28: NO/Always Det,
29: N.C., Always detected, Fast Stop
Fast-Stop
2A: N.O., During run, Fast Stop
29: NC/Always Det,
2B: N.C., During run, Fast Stop
Fast-Stop
2C: N.O., Always detected, alarm only (continue running)
2A: NO/During RUN,
2D: N.C., Always detected, alarm only (continue running)
Fast-Stop
2E: N.O., During run, alarm only (continue running)
2B: NC/During RUN,
2F: N.C., During run, alarm only (continue running)
Fast- Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only
PID Intgrl Reset
Closed: Resets the PID control integral value.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
Description
Page
80
80
80
80
80
81
81
82
82
82
82
82
82
83
83
84