E: Motor Parameters; E: Motor Parameters; E1: V/F Pattern For Motor 1 - YASKAWA Z1000U Series Programming Manual

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

A.7 E: Motor Parameters
u

E1: V/f Pattern for Motor 1

No.
(Addr.
Name
Hex)
E1-03
V/f Pattern Selection
(0302)
E1-04
Maximum Output
(0303)
Frequency
E1-05
(0304)
Maximum Voltage
<7>
E1-06
Base Frequency
(0305)
E1-07
Middle Output
(0306)
Frequency
E1-08
Middle Output
(0307)
Frequency Voltage
E1-09
Minimum Output
(0308)
Frequency
E1-10
Minimum Output
(0309)
Frequency Voltage
E1-11
Middle Output
(030A)
Frequency 2
<6>
E1-12
Middle Output
(030B)
Frequency Voltage 2
<6> <9>
E1-13
(030C)
Base Voltage
<7> <9>
<1> Parameter setting value is not reset to the default value when the drive is initialized.
<2> Default setting is dependent on parameters A1-02, Control Mode Selection and o2-04, Drive Model Selection.
<3> Default setting is determined by E5-01 in OLV/PM.
When E5-01 is set to FFFFH, the setting range for E1-04 and E1-06 is 10.0 to 400.0 Hz and the setting range for E1-09 is 0.0 to 400.0 Hz.
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
LCD Display
V/F Selection
0: 50 Hz, Constant torque 1
0: 50 Hz
1: 60 Hz, Constant torque 2
1: 60 Hz Saturation
2: 60 Hz, Constant torque 3 (50 Hz base)
2: 60 Hz Saturation
3: 72 Hz, Constant torque 4 (60 Hz base)
3: 72 Hz
4: 50 Hz, Variable torque 1
4: 50 Hz VT1
5: 50 Hz, Variable torque 2
5: 50 Hz VT2
6: 60 Hz, Variable torque 3
6: 60 Hz VT1
7: 60 Hz, Variable torque 4
7: 60 Hz VT2
8: 50 Hz, High starting torque 1
8: 50 Hz HST1
9: 50 Hz, High starting torque 2
9: 50 Hz HST2
A: 60 Hz, High starting torque 3
A: 60 Hz HST1
B: 60 Hz, High starting torque 4
B: 60 Hz HST2
C: 90 Hz (60 Hz base)
C: 90 Hz
D: 120 Hz (60 Hz base)
D: 120 Hz
E: 180 Hz (60 Hz base)
E: 180 Hz
F: Custom V/f E1-04 through E1-13 settings define the V/f
F: Custom V/F
pattern
These parameters are only applicable when E1-03 is set to F.
To set linear V/f characteristics, set the same values for E1-07
Max Frequency
and E1-09.
In this case, the setting for E1-08 will be disregarded. Ensure
that the four frequencies are set according to these rules:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
Output Voltage (V)
Max Voltage
Base Frequency
Mid Frequency A
Mid Voltage A
Note:
Min Frequency
Min Voltage
Mid Frequency B
Mid Voltage B
Base Voltage
Description
E1-05
E1-12
E1-13
E1-08
E1-10
E1-09
E1-07 E1-06 E1-11 E1-04
Frequency (Hz)
E1-07, E1-08, and E1-10 to E1-13 are not
available in OLV/PM control mode.
A.7 E: Motor Parameters
Values
Page
<1>
Default: F
58
Range: 0 to 9;
A to F
<2> <8>
Default:
Min.: 40.0 Hz
61
Max.: 400.0 Hz
<3>
<2> <4>
Default:
Min.: 0.0 V
61
Max.: 255.0 V
<5>
<2> <4>
Default:
<8>
61
Min.: 0.0 Hz
<3>
Max.: E1-04
<2>
Default:
61
Min.: 0.0 Hz
Max.: E1-04
<2>
Default:
Min.: 0.0 V
61
Max.: 255.0 V
<5>
<2> <4>
Default:
<8>
61
Min.: 0.0 Hz
<3>
Max.: E1-04
<2>
Default:
Min.: 0.0 V
61
Max.: 255.0 V
<5>
Default: 0.0 Hz
Min.: 0.0
61
Max.: E1-04
Default: 0.0 V
Min.: 0.0
61
<5>
Max.: 255.0
Default: 0.0 V
Min.: 0.0
61
<5>
Max.: 255.0
207
A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000 cimr-zu series

Table of Contents