YASKAWA Z1000U Series Programming Manual page 15

Hvac matrix low harmonic drive for hvac applications
Hide thumbs Also See for Z1000U Series:
Table of Contents

Advertisement

1.1 A: Initialization
n
A2-33: User Parameter Automatic Selection
Determines whether recently edited parameters are saved to the second half of the User Parameters (A2-17 to A2-32) for
quicker access.
No.
Parameter Name
Setting Range
Default
Determined by
A2-33
User Parameter Automatic Selection
0, 1
A1-06
Setting 0: Do not save list of recently edited parameters
Set A2-33 to 0 to manually select the parameters listed in the User Parameter group.
Setting 1: Save list of recently edited parameters
Set A2-33 to 1 to automatically save recently edited parameters to A2-17 through A2-32. A total of 16 parameters are saved
with the most recently edited parameter set to A2-17, the second most recently to A2-18, and so on. Access the User Parameters
using the Setup Mode of the HOA keypad.
Note:
User parameters are listed from A2-27 to A2-32. Parameters A2-01 to A2-26 are already listed as defined by default when in Setup Mode.
1
YASKAWA ELECTRIC SIEP C710636 10C Z1000U HVAC MATRIX Drive Programming Manual
15

Advertisement

Table of Contents
loading

This manual is also suitable for:

Z1000 cimr-zu series

Table of Contents