3.2 Standard Connection Diagram

◆ Class: 4 kV

Figure 3.2
Main circuit input
terminals
Main circuit power supply,
AC 3-phase
R
4.16 kV
S
60 Hz
T
Ground resistance:
less than 10 Ω
Control power supply
terminals
Control power supply,
AC single-phase
R
200/220 V
S
50/60 Hz
Ground resistance:
less than 100 Ω
Analog input terminals
Frequency reference
4 to 20 mA DC
Sequence input
terminals
Stop
Run
command
command
E
E
Medium-voltage
primary panel on
Operation interlock
Reserved
External fault
reset
Reserved
Sequence output
terminals
Major fault
During run
Drive ready
Minor fault
Medium-voltage
power shutdown
command
Figure 3.2 Drive Standard Connection Diagram (Example: CIMR-MV2 D6DA052)
58
R
S
T
Grounding of the
main circuit
terminal EA
Cooling fan power supply
Controller power supply
RC
ISO
AMP
SC
Grounding of the
CN4-2
control system
terminal ED
Input voltage Input current
Analog input: 2 points
-10 V to +10 V
L1
AI_1
1
L2
GND
ISO
2
L3
AMP
FG
3
1
2
(Option)
3
200/220 Vac
Digital input: 8 points
13
14
15
1
I/O
2
3
4
5
6
7
8
9
10
Output
(transfer
contact)
30
32
31
33
35
34
36
38
37
39
40
41
42
Digital output: 8 points
Relay circuit
Digital input: 8 points
Relay
board
Digital output: 8 points
(option)
(Option)
ISO
AMP
CN21, 22
CN4-1
Output
voltage
Current detection
RS-232
resistance board
Panel board
USB
RS-485
From expansion PLC board
DO
DI
Analog output: 4 points
-10 V to +10 V
AO_1
1
GND
2
FG
3
AO_2
1
GND
2
FG
3
1
2
(Option)
3
1
2
(Option)
3
Expansion PLC
board (option)
215IF
or
218IF
(Ethernet)
To panel board
RS-232
I/O or communication
board (option)
Line driver PG board
(option)
Phase-A/B/Z input
Complementary PG
board (option)
Phase-A/B/Z input
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Main circuit output
terminals
U
V
M
W
4.16kV
Digital operator
RJ-45
RJ-45
USB copy unit (option)
USB
RS-232
DriveWizard Plus MV
Terminals for inrush current
Relay circuit
26
suppression circuit (option)
27
MC ON
28
L47
L48
MC ANS
Analog output
terminals
L4
L5
Output frequency
ISO
AMP
L6
4 to 20 mA DC
L7
L8
Output current
ISO
AMP
L9
4 to 20 mA DC
Either one or two boards can be
installed by setting parameter.
L19
Phase-A signal
L20
L21
Phase-B signal
L22
L23
12 V or 5.5 V ±5%,
L24
max. 200 mA
L25
Ground
L19
Phase-A signal
L20
L21
Phase-B signal
L22
L23
12 V or 5.5 V ±5%,
L24
max. 200 mA
L25
Ground
Line driver
output PG
PG
Complementary
output PG
PG