3.6 Control Circuit Wiring
Type
Terminal
30
31
32
33
34
35
36
Sequence output
37
terminals
38
39
40
41
42
26
28
Terminals for
inrush current
27
suppression
circuit
28
L47
L48
L19
L20
L21
L22
L23
L24
L25
Terminals for
the PG
<2>
L19
L20
L21
L22
L23
L24
L25
<1> For the host breaker, AC voltage should be input.
If using DC voltage as the input power, install a relay that has contacts with a large capacity.
<2> When a PG interface is mounted, either a line driver PG interface or a complementary type PG interface is prepared.
Note: Depending on a parameter setting, either one or two boards can be inserted. In this table, it is assumed that one board is inserted.
70
Signal Name
Major fault
During run
Drive ready
Minor fault
Medium-voltage power
shutdown command
Inrush current suppression
circuit (option)
Line driver
PG interface PG-X3
(Option)
Complementary type
PG interface PG-B3
(Option)
Signal Level
Transfer contact relay
220 Vac/15 A,
110 Vac/15 A,
24 Vdc/15 A
Transfer contact relay
220 Vac/15 A,
110 Vac/15 A,
24 Vdc/15 A
Transfer contact relay
220 Vac/15 A,
110 Vac/15 A,
24 Vdc/15 A
N.O. contact relay
220 Vac/15 A,
110 Vac/15 A,
24 Vdc/15 A
N.C. contact output
220 Vac/4 A,
110 Vac/7 A
200 Vdc/4 A
100 Vdc/7 A
N.O. contact relay output
220 Vac/5.5 A,
110 Vac/10 A,
100 Vdc/0.5 A
<1>
N.C. contact relay output
220 Vac/10 A,
24 Vdc/10 A
Contact output
220 Vac/8 mA
A pulse signal input
A inverse signal input
B pulse signal input
B inverse signal input
PG power supply
PG power supply common
Ground
A+ pulse signal input
A- pulse signal input
B+ pulse signal input
B- pulse signal input
PG power supply
PG power supply common
Ground
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Terminal Function
Open: Major fault (32-31)
Closed: Major fault (32-30)
Closed: During run (35-33)
Open: During run (35-34)
Closed: Drive ready (38-36)
Open: Drive ready (38-37)
Closed: Minor fault
Closed (N.C.): Turning off
(closed when power is off)
MC_ON signal
(Output in response to Drive
Ready)
MC_ANS signal
(Closed by answer from inrush
current suppression panel)
Inputs the A and B signals
Signal levels: Equivalent to RS-422
Output voltage:
12 V ± 5% or 5.5 V ± 5%
Max. output current: 200 mA
Grounds shielded lines
Inputs the A and B channel
Signal levels: High level: 8 to 12 V
Low level: 2.0 V or less
Output voltage: 12 V ± 5%
Max. output current: 200 mA
Grounds shielded lines