4.6 Auto-Tuning
Setting 1: Motor 1
Auto-Tuning automatically sets parameters E1-
Setting 2: Motor 2
Auto-Tuning automatically sets parameters E3-
drive for Auto-Tuning.
T1-01: Auto-Tuning Mode Selection
Sets the type of Auto-Tuning to be used.
Note: When running multiple motors, Auto-Tuning is not possible.
No.
T1-01
Auto-Tuning Mode Selection
Setting 0: Rotational Auto-Tuning
Setting 2: Stationary Auto-Tuning for Line-to-Line Resistance
T1-02 Motor Rated Capacity
Sets the rated capacity of the motor according to the value on the motor nameplate.
No.
T1-02
Motor Rated Power
T1-03: Motor Rated Voltage (T1-01 = 0, 1, 3, 4)
Sets the motor rated voltage according to the motor nameplate value. If the motor to be operated above its base speed,
enter the voltage at base speed here.
For better control precision around rated speed when using a vector control mode, it can be helpful to enter the no-load
voltage for the motor here. The motor's "no-load voltage" refers to the voltage needed to operate the motor under no-load
conditions at rated speed. The no-load voltage can usually be found in the motor test report available from the
manufacturer. If no data is available, enter approximately 90% of the rated voltage printed on the motor nameplate.
No.
T1-03
Motor Rated Voltage
T1-04: Motor Rated Current
Sets the motor rated current according to the motor nameplate value. For optimal performance in OLV or CLV, the motor
rated current should be between 50 and 100% of the drive rated current. Enter the current at the motor base speed.
No.
T1-04
Motor Rated Current
T1-05: Motor Base Frequency
Sets the motor rated frequency according to the motor nameplate value. If a motor with an extended speed range is used
or the motor is used in the field weakening area, enter the maximum frequency to E1-04 (E3-04 for motor 2) after Auto-
Tuning is complete.
No.
T1-05
Motor Base Frequency
98
and E2-
and E4-
Auto-Tuning Type on page 94
Name
Name
Name
Name
Name
for motor 1.
for motor 2. Make sure that motor 2 is connected to the
for details on the different types of Auto-Tuning.
Setting Range
2 (V/f)
0, 2 (OLV, CLV)
Setting Range
0 to 65000 kW
Setting Range
0 to 13000 V
Setting Range
(n9-01) × 0.1 to (n9-01)
× 2
Setting Range
0.0 to 120.0 Hz
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Default
2 (V/f)
0 (OLV, CLV)
Default
Determined by o2-04
Default
Determined by A1-02
and o2-04
Default
Determined by o2-04
Default
60.0 Hz