Password (A1-04, A1-05); Copy Function - YASKAWA FSDrive-MV1000 Instructions Manual

Super energy-saving medium-voltage ac drive
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

4.9 Verifying Parameter Settings and Backing Up Changes
No.
Name
A2-01
to
User Parameters 1 to 32
A2-32
User Parameter Automatic
A2-33
Selection

◆ Password (A1-04, A1-05)

If a password is set in A1-05, the password must be verified by A1-04. Validate and enter correct password. Otherwise,
parameters A1-01 to A1-03 and A2-01 to A2-33 cannot be changed.
Note: A1-05 is normally not displayed. To display and configure settings, display A1-04, and press
digital operator.

◆ Copy Function

The drive's parameter setting can be copied into other drive using the digital operator of main body or optional device.
This allows you to easily save the parameter setting and set up multiple drives.
• Digital Operator (supplied with this product)
This enables to read/copy/verify the parameters in addition to the basic operation of the drive.
For more information on the operation procedure, refer to
on page
105.
• USB Copy Unit
Allows you to connect to the drive, read the drive's parameter setting, and copy the setting into other drive. Refer to the
USB Copy Unit Installation Manual for details of operation procedure.
Note: Connect to the drive's operator connector.
• CopyUnitManager
Allows you to manage multiple parameter settings read with the USB Copy Unit. This increases the efficiency of
writing parameters to drives of different capacities and different models.
For more information on the operating procedure, refer to the operation manual for the CopyUnitManager.
• DriveWizard Plus MV
This is a computer software package used for drive parameter management, monitoring and self-diagnosis.
Allows you to load/save parameter settings, and to copy them to other drives.
For more information on the operating procedure, refer to the operation manual supplied with the DriveWizard Plus
MV software.
104
Description
Function that automatically saves the parameters and their
values edited recently and allows the user to select the
parameters that are used frequently.
When A2-33 is set to "1", the parameters and their values
edited recently are automatically selected for A2-17 through
A2-32 in sequence. (A2-01 through A2-16 must be set
manually.)
When A2-33 is "0", automatic selection of edited parameters
is not performed. Users must register all in A2-01 through A2-
32.
0: Do not save list of recently viewed parameters. (Parameters
of A2-01 through A2-32 must be selected by the user.)
1: Save history of recently viewed parameters. (Recently
edited parameters will be saved to A2-17 through A2-32. The
most recently edited parameters are automatically selected for
A2-17. Those edited after the most recently edited parameters
are selected for A2-18.)
Operation Procedure of Copy Function (Digital Operator)
Setting
Range
b1-01 to
o -
0, 1
while pressing
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Default
1