4.4 Start-Up Flowcharts

◆ Subchart A-2: High Performance Operation Using OLV or CLV

Subchart A-2 describes the setup procedure when using Open Loop Vector Control or Closed Loop Vector Control.
Vector control is appropriate for applications requiring a high starting torque and torque limits.
Note: Although the drive sets parameters for the PG encoder during Auto-Tuning, sometimes the direction of the motor and direction
of the PG get reversed. Use parameter F1-05 to switch the direction of the PG so that it matches the motor direction.
Figure 4.10
Use the following functions?
• Feed forward control
• Single Drive KEB Ride-Thru 2 (L2-29 = 1)
• Sequence input: KEB Ride-Thru 2 (N.C.) (H1-
Run the machine and check for desired operation.
<1> Check to see that the brake is released.
92
From
Flowchart
A
YES
Possible for motor to
rotate during tuning?
<1>
NO
NO
Is
YES
the motor
cable longer than 50
meters?
NO
Is there a PG encoder
on the motor?
YES
= 7A)
Turn on the main circuit power.
Return to
Flowchart
A
Figure 4.10 High Performance Operation Using OLV or CLV
YES
Is the load less than
30% of the rated load
for the motor?
Perform Stationary Auto-Tuning.
(T1-01 = 2)
NO
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Perform Rotational
Auto-Tuning (T1-01 = 0).