YASKAWA FSDrive-MV1000 Instructions Manual page 141

Super energy-saving medium-voltage ac drive
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

Digital Operator Display
oPE06
Cause
A control mode has been selected that
requires a PG option card to be installed (A1-
02 = 3), but no PG option card is installed.
Digital Operator Display
oPE07
Cause
At least two analog input terminals are set to
the same function (i.e., at least two of these
parameters has the same setting: H3-02 and
H3-10).
The following simultaneous contradictory
settings:
H3-02 and H3-10 = C (PID Target Value)
while b5-18 = 1 (enables b5-19 as the target
PID value)
Digital Operator Display
oPE08
Cause
Attempted to use a function that is not valid
for the selected control mode.
In Open Loop Vector Control, n2-02 is
greater than n2-03
In Open Loop Vector Control, C4-02 is
greater than C4-06
Note: Use U1-18 to find which parameters are set outside the specified setting range.
Other errors are given precedence over oPE08 when multiple errors occur at the same time.
Digital Operator Display
oPE09
Cause
The following simultaneous contradictory
settings have occurred:
• b5-15 not 0.0 (PID Sleep Function Start
Level)
• The stopping method is set to either DC
Injection Braking or coast to stop with a
timer (b1-03 = 2 or 3).
When b5-01 = 1 or 2 (PID output 1/2), d2-02
(Frequency Reference Lower Limit)
specified.
When b5-01 = 1 or 2 (PID output 1/2), b5-11
(PID Output Reverse Selection) = 1 (Rotation
direction reverses with negative PID output)
was specified.
PID control is set to b5-01 = 3 or 4, but the
lower limit for the frequency reference (d2-
01) is not 0.
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Control Method Selection Error
Correct the setting for the control method.
⇒Connect a PG option card.
⇒Correct the value set to A1-02.
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10 and PID
functions conflict.
Change the settings to H3-02 and H3-10 so that functions no longer conflict.
Note: Both 0 (frequency reference bias) and F (not used) or 1F (Through mode) can be set
to H3-02 and H3-10 at the same time.
Disable one of the PID selections.
Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.
⇒Check the motor control method and the functions available.
⇒Correct parameter settings so that n2-02 is less than n2-03.
⇒Correct parameter settings so that C4-02 is less than C4-06.
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1
to 4).
⇒Set b5-15 to another value besides 0.
⇒Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
⇒Correct the parameter settings.
0 was
⇒Correct the parameter settings.
⇒Correct the parameter settings.
5.6 Operator Programming Error
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
5
141