Digital Operator Display
CPF00, CPF01
<1>
CPF20, CPF21
<1>
Cause
There is a self diagnostic error in control
circuit.
Connector on the operator is damaged.
Digital Operator Display
CPF02
Cause
Control circuit is damaged.
Digital Operator Display
CPF06
Cause
There is an error in EEPROM control circuit.
The control power supply was switched off while
parameters were being saved to the drive (while
the communication option card was in use).
Digital Operator Display
CPF22
Cause
Hybrid IC on the main circuit is damaged.
Digital Operator Display
CPF23
Cause
Hardware is damaged.
Digital Operator Display
CPF26 to CPF35
CPF40 to CPF45
Cause
Hardware is damaged.
Digital Operator Display
dEv
Cause
Load is too heavy.
Acceleration and deceleration times are set
too short.
The load is locked up.
Parameters are not set appropriately.
The mechanical holding brake is applied to
the motor.
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Control Circuit Error
Cycle control power to the drive.
⇒If the problem continues, replace the control board. For instructions on replacing it,
contact Yaskawa or your nearest sales representative.
⇒Replace the operator.
A/D Conversion Error
An A/D conversion error or control circuit error occurred.
Cycle control power to the drive.
⇒If the problem continues, replace the control board. For instructions on replacing it,
contact Yaskawa or your nearest sales representative.
EEPROM Memory Data Error
There is an error in the data saved to EEPROM.
Cycle control power to the drive.
⇒If the problem continues, replace the control board. For instructions on replacing it,
contact Yaskawa or your nearest sales representative.
⇒Reinitialize the drive (A1-03 = 2220).
Hybrid IC Error
• Cycle control power to the drive.
• If the problem continues, replace either the control board or the entire drive. For instructions
on replacing the control board, contact Yaskawa or your nearest sales representative.
Control Board Connection Error
Connection error between the control board and the Power Cell
• Turn off the power for the main circuit and controls and check the connection between the
control board and the Power Cell.
• If the problem continues, replace either the control board or the entire drive. For instructions
on replacing the control board, contact Yaskawa or your nearest sales representative.
Control Circuit Error
⇒Replace the cell control board. For instructions on replacing it, contact Yaskawa or your
nearest sales representative.
Speed Deviation (for Control Mode with PG)
The deviation between the speed reference and speed feedback is greater than the setting in
F1-10 for longer than the time set to F1-11.
Check the size of the load.
⇒Reduce the load.
⇒Increase the acceleration and deceleration times (C1-01 through C1-08).
⇒Check the machine.
⇒Check the settings of parameters F1-10 and F1-11.
⇒Ensure the motor brake releases properly.
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Refer to Diagnosing and Resetting Faults on page
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
5.4 Fault Detection
150.