5.6 Operator Programming Error
Digital Operator Display
oPE10
Cause
V/f Pattern Setting Error
Digital Operator Display
oPE15
Cause
When A1-02 = 3 (Closed loop vector
control), the following setting is specified.
• The torque control selection is specified at
the same time. d5-01=1 and H1-
• DROOP control and feed forward control
are enabled when torque control is selected:
d5-01 = 1 or H1-
= 71, and also b7-01
0 or n5-01 = 1.
• KEB command 2 (N.O. input, N.C. input)
is enabled when torque control is selected:
d5-01 = 1 or H1-
=71 and also H1-
= 7A or H1-
= 7b.
• The optimal deceleration and
overexcitation deceleration 2 are enabled
when torque control is selected.(d5-01=1 or
H1-
=71) and (L3-04=2 or L3-04=5)
Digital Operator Display
oPE18
Cause
One of the following settings has occurred
while Online Tuning is enabled (n6-01 = 2) in
Open Loop Vector control (A1-02 = 2).
• E2-02 has been set below 30% of the
original default value
• E2-06 has been set below 50% of the
original default value
• E2-03 = 0
142
V/f Data Setting Error
The following setting errors have occurred where:
• E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
• E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11 (for motor 2, correct E3-04,
E3-06, E3-07, E3-09, and E3-11).
Torque Control Setting Error
Parameters settings that are not allowed in combination with Torque Control have been set.
=71
⇒Correct the settings of b7-01, d5-01, H1-
Online Tuning Parameter Setting Error
Parameters that control Online Tuning are not set correctly.
Make sure E2-02, E2-03, and E2-06 are set the correct values.
Error Name
Possible Solutions
Error Name
Possible Solutions
, L3-04 and n5-01.
Error Name
Possible Solutions