Advertisement

5.6 Operator Programming Error
Settings for N.C. and N.O. input for the
following functions were selected at the same
time:
• External Search Command 1 and External
Search Command 2 (61 vs. 62)
• Fast Stop N.O. and Fast Stop N.C. (15 vs.
17)
• Motor Switch Command and Accel/Decel
Time 2 (16 vs. 1A)
• FWD Run Command (or REV) and FWD/
REV Run Command (2-wire) (40, 41 vs.
42, 43)
• External DB Command and Drive Enable
(60 vs. 6A)
• Motor Switch Command and Up 2/Down 2
Command (16 vs. 75, 76)
One of the following settings was entered
while H1-
= 2 (External Reference 1/2):
• b1-15 or b1-16 set to 3 but no option card
is connected
• b1-15 = 1 (Analog Input) and H3-02
(Analog Input Function Selection) is not set
to 0 (Analog Frequency Reference).
H2-
= 38 (Drive Enabled) but H1-
not set to 6A (Drive Enable).
A signed value (H3-01) is set for the analog
input while allocating the UP2/DOWN2
commands (75 and 76).
Digital Operator Display
oPE05
Cause
Frequency reference is assigned to an option
card (b1-01 = 3) but an input option card is
not connected to the drive.
The Run command is assigned to an option
card (b1-02 = 3) but an input option card is
not connected to the drive.
Although the digital card input is set for BCD
special for a 5 digit input (F3-01 = 6), the
data length is set for 8 bit or 12 bit (F3-03 =
0, 1).
The following values have been set while an
AI-A3 option card is installed:
• The source of frequency reference setting
is assigned to an option card (b1-01 = 3).
• The action for the analog card is set for
separate terminal input (F2-01 = 0).
The content below is set at the same time but
AI-A3 option is not connected.
• b1-16 (Run Command Selection 2) = 3
(Option card)
• H1-
= 2 (External reference 1/2
selection)
140
Check for contradictory settings assigned to the multi-function input terminals at the same
time.
⇒Correct the sequence input settings.
Check for contradictory settings assigned to the multi-function input terminals at the same
time.
⇒Correct the sequence input settings.
is
⇒Cancel either setting.
Run Command/Frequency Reference Source Selection Error
The setting for executing a Run command or frequency reference from communication
option card input is not correct.
⇒Reconnect the input option card to the drive.
⇒Set the input data for 16 bit (F3-03 = 2).
⇒Make sure parameters are set properly.
⇒Make sure parameters are set properly.
Error Name
Possible Solutions