5.7 Auto-Tuning Fault Detection
Digital Operator Display
End7
Cause
The entered no-load current value was outside
the allowable range.
Auto-Tuning results were less than 5% of the
motor rated current.
Digital Operator Display
Er-01
Cause
Motor data or data entered during Auto-
Tuning was incorrect.
Motor output power and motor-rated current
settings (T1-02 and T1-04) do not match.
Motor rated current and detected no-load
current are not consistent with another.
Base frequency and motor rated speed (T1-05
and T1-07) do not match.
Digital Operator Display
Er-02
Cause
Motor data or data entered during Auto-
Tuning was incorrect.
Wiring is incorrect.
Load is too heavy.
Digital Operator Display
Er-03
Cause
Auto-Tuning canceled by pressing STOP
button.
Digital Operator Display
Er-04
Er-05
Er-08
Cause
Motor data or data entered during Auto-
Tuning was incorrect.
The tuning process took too long.
Results from Auto-Tuning are outside the
parameter setting range.
Digital Operator Display
Er-09
Cause
The motor did not accelerate for the specified
acceleration time.
Torque limit when motoring is too low (L7-01
and L7-02).
144
No-Load Current Alarm
⇒Check and correct faulty motor wiring.
⇒Double check the data that was entered for the Auto-Tuning process.
Motor Data Error
Check that the motor data entered to T1 parameters matches motor nameplate input before
Auto-Tuning.
⇒Enter the correct information and start Auto-Tuning over again.
Check the drive and motor capacities.
⇒Correct the settings of parameters T1-02 and T1-04.
Check the motor rated current and no-load current.
⇒Correct the settings of parameters T1-04 and E2-03.
⇒Set T1-05 and T1-07 to the correct value.
Minor Fault
Check that the motor data entered to T1 parameters matches motor nameplate input before
Auto-Tuning.
⇒Enter the correct information and start Auto-Tuning over again.
⇒Check and modify the wiring.
⇒Check the circumference of the machine.
⇒Check the load.
STOP Button Input
⇒Auto-Tuning did not complete properly and will have to be performed again.
Line-to-Line Resistance Error
No-Load Current Error
Rated Slip Error
Check that the motor data entered to T1 parameters matches motor nameplate input before
Auto-Tuning.
⇒Start Auto-Tuning over again and enter the correct information.
⇒Check and correct faulty motor wiring.
⇒Disconnect the motor from machine and perform Rotational Auto-Tuning.
Acceleration Error (detected only during Rotational Auto-Tuning)
⇒Increase the acceleration time (C1-01).
⇒Disconnect the machine from the motor, if possible.
Check the settings of parameters L7-01 and L7-02.
⇒Increase the setting.
Error Name
Possible Solution
Error Name
Possible Solution
Error Name
Possible Solution
Error Name
Possible Solution
Error Name
Possible Solution
Error Name
Possible Solution
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents