DEFINED CONTENTS OF CONFIGURABLE INPUT PORTS

Table 9 Defined Contents of Programmable Inputs 1~5 (All are ground-connectedly active.)
No
Items
0
Not Used
High
Temperature
1
Shutdown
Low
Oil
2
Shutdown
3
External Warning Input
4
Emergency Stop Alarm
Water Temp. High Stop
5
by Cool
Generator
6
Auxiliary
7
Reserved
Inhibit Water Temp. High
8
Stop
Inhibit Oil Pressure Low
9
Stop
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
When warning and shutdown alarms appear, audible alarm output
is fixed as 300s, during the time whether press any key on the
panel or Alarm Mute input is active, it can remove the alarm.
Controlled by the temp. sensor by heating according to the upper
and lower limit;
Output when genset is in start status; and disconnect in other
status.
Used for ECU engine to control its stop.
Used for ECU engine to control the power.
Indicate ECU sends a warning signal.
Indicate ECU sends a shutdown signal.
Indicate controller cannot communicates with ECU.
Speed rise time when genset enters into high-speed warming up
period.
Speed drop time when genset enters into high-speed warming up
period.
If these signals are active after safety on delay, shutdown alarm
will be immediately initiated.
Pressure
If it is active, it is only warning, not shutdown.
Shutdown alarm will be immediately initiated if this input is active.
When the gen-set is running normally and this signal is activated,
if there is a high temperature situation, the controller will first cool
down the generator and then stop it; if the signal is deactivated
and a high temperature situation occurs, the controller will shut
down the gen-set without cooling down.
Closed
Connected to the auxiliary switch of the generator with loading.
When it is active, prohibit stopping when high temperature occurs.
Details to see Parameter Setting
When it is active, prohibit stopping when low oil pressure occurs.
Details to see Parameter Setting
2019-01-28
Description
Description
NOTE 2.
NOTE 3.
Version1.0
Page 29 of 48