PARAMETER SETTING
8.1

CONTROLLER PARAMETER SETTING

Start the controller, and then press
as follows:
1
Set Parameters
2
Information
3
Set Language/语言
4
Event Log
5
Maintenance
When password "0318" is inputted, all parameter items in Table 7 can be set. If the password
"0318" has been changed, when users conduct parameter setting via PC, they have to input the
same password as the controller. If it is needed to set more items or the password is forgotten, for
example, voltage/current calibration, please contact the factory.
NOTES:
a) Please change the controller parameters when generator is in standby mode only (e. g. Crank disconnection
condition selection, auxiliary input, auxiliary output, various delays), otherwise, shutdown and other abnormal
conditions may occur.
b) Over voltage set value must be higher than under voltage set value, otherwise over voltage and under voltage
conditions may occur simultaneously.
c) Over speed set value must be higher than under speed set value, otherwise over speed and under speed
conditions may occur simultaneously.
d) Please set the generator frequency value as low as possible at the moment of cranking. It is supposed to make
the starter be separated quickly as soon as possible.
e) Auxiliary inputs 1~5 could not be set as the same item; otherwise, there are abnormal functions. However, the
auxiliary outputs 1~5 can be set as the same item.
f) Programmable sensor 1 input port can be set as fuel level sensor or digital input port 4; programmable sensor 2
input port can be set as temperature sensor, pressure sensor, coolant level sensor or digital input port 5. Either
the sensor or the digital input port is Ok, and if digital input port is selected, the corresponding set parameters
shall be functional and sensor parameters are inactive and reserved; otherwise, if the sensor is selected, the
corresponding sensor parameters shall be functional and digital input port parameters are deactive and reserved.
g) If it is needed to shut down after cooling, please set any auxiliary input as "High Temperature Stop Input", then
connect this input port to GND or set "High Temperature Stop Input" action as "Cooling Stop".
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
to enter the parameter setting menu. Menu items are
2019-01-28
Version1.0
Page 33 of 48