SENSOR SETTING

─ If a sensor is needed to be changed again, the sensor curve will be transferred into the standard
value. For example, if the default temperature sensor is SGH (120° C resistor type), the sensor
curve is SGH curve (120° C resistor type); if it is set SGD (120° C resistor type), the temperature
sensor curve is SGD curve.
─ If there is difference between standard sensor curve and the used sensor, users can choose
"defined sensor", and input "defined sensor curve".
─ At the time of inputting the sensor curve, X value (resistor) must be inputted from small to large,
otherwise, any mistake may occur.
─ If there is not an oil pressure sensor, and there is only a low oil pressure alarm switch, then the
pressure sensor must be set "None", otherwise, low oil pressure shutdown alarm may occur.
─ It is applicable to set the headmost and backmost values in the vertical coordinate as the same
as the Figure 3.
1Pa
2
1kgf/cm
1bar
1psi
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
Fig. 3 Sensor Curve Graph
Table 12 Common Pressure Conversion Table