7.2

DEFINABLE CONTENTS OF PROGRAMMABLE OUTPUT PORTS

Table 8 Definable Contents of Programmable Output Ports 1~5
No
Items
0
Not Used
1
Common Alarm
2
Energize to Stop
3
Idle Control
4
Preheat Control
5
Close Generator Output
6
Reserved
7
Open ATS
8
Raise Speed Control
9
Drop Speed Control
10
Generator Run Output
11
Fuel Pump Control
12
High Speed Control
13
In Auto Mode
Fuel Relay Output
14
15
Excite Generator
16
Cooler Output
17
Louver Control
18
Shutdown Alarm Output
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
Output port is deactivated when "Not Used" is selected.
It includes all shutdown alarms and warning alarms. When there
is warning alarm only, it is not self-lock; when a shutdown alarm
occurs, it is self-lock until the alarm is reset.
Suitable for genset with electromagnet; it shall pull in after end of
"stop idle delay". It is deactivated when the "ETS Solenoid delay"
expires.
Used for engine with idling speed; it shall pull in when the genset
starts; it disconnects when the genset enters warming up time; it
shall pull in in the process of stop idling speed; it shall open when
the genset stops completely.
Close before the genset starts and open before the starter is
energized;
When the close time is 0, it's continuous output.
When the close time is 0, it's disabled.
Close when the generator enters into Warming Up time; the pull-in
time is the warming up time.
Close when the generator enters into idling speed stop process or
ETS stop process (shutdown alarm time); the pull-in time is the
idling speed stop delay time.
Act when genset is normal running; disconnect when the speed is
lower than the crank disconnection speed;
Close when the fuel level is lower than the "Fuel Pump On" value
or the low fuel level warning input is active; Open when the fuel
level is higher than the "Fuel Pump Off" and the low fuel level
warning input is deactivated;
Close when the generator enters into Warming Up time; Open
after cooling time;
The controller is in automatic mode.
Act when generator starts; disconnect when the generator is
waiting for a complete stop;
Output when the generator starts; Output for 2s if there is not
generator frequency during safe running period;
Control air cooler's start\stop according to cooler temperature;
Act in genset starting and disconnect when genset stops
completely.
Output when shutdown alarms appear.
2019-01-28
Description
Version1.0
Page 28 of 48