No
Items
Gen
Over
Freq
85
Warning
Gen
Under
Freq
86
Warning
Gen Over Current
87
Warning Percentage
High Water Temp.
88
Warning
Low Oil Pressure
89
Warning
Flexible
Sensor
90
Warning
Gen Over Volt Delay (0-20.0)s
91
Gen
Over
92
Frequency Delay
Oil Pressure Delay
93
at successful start
94
Scheduled Run Set
Cycle
Scheduled
95
Run Set
HGM4100LT Genset Controller
HGM4100LT GENSET CONTROLLER USER MANUAL
Range
Default
(0-75.0)Hz
55.0
(0-75.0)Hz
42.0
(50-130)%
110
95
(80-300)℃
(0-400)kPa
124
(80-300)º C
(0-400)kPa
95
(0-100)%
10.0
(0-20.0)s
2.0
(0-20.0)s
0.0s
(0-1)
0
(0-1)
0
(0-2)
0
(1-31)
1
(0-7)
0
(1-23)h
0
(1-59)min
0
(0-30000)min
30
2019-01-28
Description
When generator frequency exceeds the pre-set
value, gen over frequency warning signals will
be sent.
When generator frequency is below the pre-set
value, gen under frequency warning signals will
be sent.
When generator current exceeds the pre-set
value, gen over current warning signal will be
sent. (No warning alarm is sent if the value is
set 0.)
When the value of external temperature sensor
exceeds the pre-set value, high temperature
signal shall be sent. It is only for the
temperature sensor externally connected; No
warning alarm is sent if the value is set 300 (it is
only for temp. sensor, and the signal of digital
inputs are not included).
When the value of external pressure sensor is
below the pre-set value, low oil pressure delay
starts; it only judges after end og Safe Running
delay; No warning alarm is sent if the value is
set 0 (it is only for pressure sensor, and signal
of digital inputs are not included).
Respectively corresponding to 88(Temperature
Sensor set), 89(Pressure Sensor set), 82(Level
Sensor set) in this table;
When generator volt is higher than the pre-set
shutdown value and the "over volt" delay has
expired, then it can be considered as gen over
volt shutdown.
When generator frequency is higher than the
shutdown
pre-set
frequency" delay has expired, then it can be
considered as gen over frequency shutdown.
When crank disconnection condition contains
oil pressure, and oil pressure of engine exceeds
the preset crank disconnection value, and the
delay has expired, then it can be considered as
genset successful start and starter will be
disconnected.
0: Enabled inhibit
0: Off load
Cycle options: 0:monthly 1:Weekly 2:Daily
Day(Cycle options: 0: monthly active)
Week(Cycle options: 0: weekly active)
Start time(hour)
Start time(minute)
Lasting time
Version1.0
value
and
the
"over
1: Enabled
1: On load
Page 25 of 48